26
Securing the refrigerant lines:
■
Secure refrigerant lines using only pipe clips with soft
elastic insulating lining (EPDM).
■
Secure the pipe bend for vibration compensation at
the end of the bend with a pipe clip (towards the
external wall).
■
Secure refrigerant lines with pipe clips at intervals of
max. 2.0 m. We recommend securing the refrigerant
lines with pipe clips at intervals of 1.5 m.
■
Recommendation: Mount pipe clips only on compo-
nents with a mass per unit area ≥ 250 kg/m
2
.
■
Do not install refrigerant lines on partition walls or
ceilings to rooms that require a low noise level (e.g.
bedrooms).
Installation sequence
Connecting the refrigerant lines (cont.)
6199592
Installation