75
External changeover of the operating status of various system components
Parameter Setting
"System definition" Ó
"System components for external changeover 7011" "0" to "127"
"Operating status for external changeover 7012" "0" to "3"
"Duration of external changeover 7013" "0" to "12"
External blocking of compressor and pumps
Parameter Setting
"System definition" Ó
"Effect of external blocking on pumps/compressor 701A" "0" to "31"
External blocking of the compressor; mixer in control mode or CLOSED
Parameter Setting
"System definition" Ó
"Effect of ext. blocking on heat pump/heating circuits 7015" "0" to "8"
"Effect of external blocking on pumps/compressor 701A" "0" to "31"
External hook-up for heating/cooling circuits
Parameter Setting
"Heating circuit 1"/"Heating circuit 2"/"Heating circuit 3" Ó
"Remote control 2003"
or
"Remote control 3003"
or
"Remote control 4003"
"2"
Type AWBT(-M)-AC/AWBT(-M)-E-AC: Parameters for cooling function
Cooling function on systems without buffer cylinder
Parameter Setting
"Cooling" Ó
"Cooling function 7100" "3"
"Cooling circuit 7101" "1" Heating circuit HC1
"2" Heating circuit HC2
"3" Heating circuit HC3
"4" Separate cooling circuit SKK
Room temperature sensor for separate cooling circuit
Parameter Setting
"Cooling" Ó
"Ranking room temp sensor separate cooling circuit 7106" "0" Connection F16
"1" Heating circuit HC1
"2" Heating circuit HC2
"3" Heating circuit HC3
"4" Do not adjust.
Commissioning, inspection, maintenance
Commissioning the system (cont.)
6199592