Parameters for instantaneous heating water heater
Parameter Setting
"Electr booster heater" Ó
"Enable instantaneous heating water heater 7900" "1"
"Output for instant. heating water heater at power-OFF 790A" "1" 3 kW
"2" 6 kW
"3" 9 kW
!
Please note
After value "1" has been set for "Enable
instantaneous heating water heater 7900",
the enquiry "Secondary circuit filled?"
appears automatically. If this enquiry is respon-
ded to with "No", the instantaneous heating
water heater will not be enabled. Set "Enable
instantaneous heating water heater 7900" to
"2".
Fill the secondary circuit. Confirm prompt "Sec-
ondary circuit filled?" with "Yes".
Enable instantaneous heating water heater for DHW heating
Parameter Setting
"DHW" Ó
"Enable electric heaters for DHW heating 6015" "1"
Parameters for swimming pool water heating
Parameter Setting
"System definition" Ó
"External extension 7010" "1" or "3"
"Swimming pool 7008" "1"
Parameters for ventilation with Vitovent 200-C
Parameter Setting
"Ventilation" Ó
"Vitovent enable 7D00" "2" Vitovent 200-C
Commissioning, inspection, maintenance
Commissioning the system (cont.)