Technical Data
4
4 VITOCELL 100-V
Technical Data
For domestic hot water heating applications in Suitable for heating systems with
conjunction with hot water heating boilers H max. working pressure on the heat exchanger side of up to 150 psig / 10 bar
H max. working pressure on DHW side of up to 150 psig / 10 bar
H max. supply temperature on the heat exchanger side of up to 230 °F / 110 °C
H max. DHW supply temperature of up to 150 °F / 65.6 °C
Storage Capacity USG
ltr
42
160
53
200
79
300
119
450
Recovery rate
*1
with a temperature rise
of the domestic hot
194 °F
90 °C
MBH
GPM
ltr/h
136
4.3
982
136
4.3
982
180
5.7
1302
238
7.6
1720
water from
50 to 113 °F /
10 to 45 °C
176 °F
80 °C
MBH
GPM
ltr/h
109
3.5
786
109
3.5
786
150
4.8
1081
198
6.3
1425
temperature of.... at the
supply flow rate stated
158 °F
70 °C
MBH
GPM
ltr/h
85
2.7
614
85
2.7
614
113
3.6
811
153
4.9
1106
140 °F
60 °C
MBH
GPM
ltr/h
58
1.8
417
58
1.8
417
78
0.3
565
109
3.5
786
122 °F
50 °C
MBH
GPM
ltr/h
31
1
221
31
1
221
61
1.9
442
82
2.6
589
Recovery rate
*1
with a temperature rise
of the domestic hot
194 °F
90 °C
MBH
GPM
ltr/h
123
2.7
619
123
2.7
619
153
3.4
774
181
4
911
water from
50 to 140 °F /
10 to 60 °C
176 °F
80 °C
MBH
GPM
ltr/h
95
2
482
95
2
482
116
2.6
584
150
3.3
756
temperature of.... at the
supply flow rate stated
below
158 °F
70 °C
MBH
GPM
ltr/h
65
1.4
327
65
1.4
327
78
1.7
395
113
2.5
567
Supply flow rate for the
recovery rates stated
GPM
m
3
/h
13.2
3.0
13.2
3.0
13.2
3.0
13.2
3.0
Standby losses
*2
MBH/24 h 5.1 5.8 7.5 9.6
Overall dimensions with insulation
Width (∅) inches
mm
Depth inches
mm
Height inches
mm
Tilt height inches
mm
23
581
24
608
47
1189
50
1260
23
581
24
608
55½
1409
57½
1460
25
633
27¾
705
68¾
1746
70½
1792
33½
850
35¼
898
77
1955
73¼
1860
Weight
Tank with insulation
lbs
kg
190
86
214
97
333
151
399
181
Heating water content USG
ltr
1.45
5.5
1.45
5.5
2.6
10
3.3
12.5
Heat exchanger surface area ft.
2
m
2
10.8
1
10.8
1
16.1
1.5
20.5
1.9
Connections
Heating water supply/return
∅” (male thread) 1
1
1
1
∅
Recirculation
∅” (male thread) ¾
¾
1
1
*1
When planning for the recovery rate as stated or calculated, allow for the corresponding circulation pump. The stated recovery rate is
only achieved when the rated output of the boiler is equal to or greater than that stated under “Recovery rate”.
Please also refer to the corresponding sizing chart at the end of this manual.
*2
Measured values are based on a room temp. of 68°F / 20 ºC and a domestic hot water temp. of 149°F / 65 ºC and can vary by 5%.