EasyManua.ls Logo

Viessmann VITOTRANS 222 - Specification

Viessmann VITOTRANS 222
20 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
18
Serial no. 7537 157 7537 158 7537 159
Transferable heating output at
75 °C heating water flow temperature/
35 °C heating water return temperature and
10 °C cold water inlet temperature/
60 °C DHW outlet temperature
kW up to 80 up to 120 up to 240
Content
Heating water l 1.7 2.3 4.0
DHW l 1.7 2.3 4.0
Connections (DIN 2999)
Heating water flow and return R 1 1 1¼
Cold water, DHW R 1 1 1¼
Weight kg 25 27 60
Permiss. operating pressure
Heating water and DHW sides
bar
MPa
10
1
10
1
10
1
Power consumption per pump
On the primary/secondary side
■
Min. W 3 3 8
■
Max. W 45 45 130
Max. heating water temperature
With mixer assembly (for modulating operation) °C 110 110 110
Without mixer assembly (for constant operation) °C 75 75 75
Specification
Specification
5549 892 GB