V10-DRAIN
V10-DRAIN
INSTALLATION AND OPERATION
2 pump multifunction controller
for 1/3-phase pumps up to 5,5 kW
(control by 4-20 mA submersible level transducer)

Questions and Answers

  • S
    Scott WrightAug 9, 2025
    What to do if VIGILEC Water Pump alarm trips?
    • T
      Terry MorrisAug 9, 2025
      If the VIGILEC Water Pump alarm trips, there could be several reasons: * The overcurrent adjustment might be too low. In this case you should check the motor consumption and adjust the current. * There might be an input phase failure. Check the three supply phases. * The motor consumption could be abnormally excessive, indicating the pump motor is overloaded. Verify the pump. * Low current consumption (less than 0.5 A) may be the reason. Check the pump. * If the Klixon input is not in use, short-circuit the non-used Klixon inputs.
  • J
    Joshua CampbellAug 23, 2025
    What to do if VIGILEC Water Pump display shows “Err-SEn” message?
    • C
      Charles BishopAug 23, 2025
      If the display shows “Err-SEn” message on your VIGILEC Water Pump, it could be due to: * The transducer not being connected. Connect the 4-20 mA transducer. * Transducer current being less than 2 mA. Check the transducer.