EasyManua.ls Logo

Vimpex Hydrosense HSCP - User Manual

Vimpex Hydrosense HSCP
18 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
Hydrosense HSCP
Conventional Water Detection
Control Panel
Operation and Maintenance Manual
Man-1131 Issue 01 November 2009
www.acornfiresecurity.com
www.acornfiresecurity.com
Question and Answer IconNeed help?

Do you have a question about the Vimpex Hydrosense HSCP and is the answer not in the manual?

Summary

Introduction

Safety and Mounting

Mounting

Instructions for securely fixing the control panel to a suitable surface at eye height.

Technical Specifications

Control Panel Fascia

Removing the Fascia

Procedure for safely removing and refitting the control panel's front fascia for access.

Connecting to the Circuit Board

Terminal Designations

Explanation of the labels and functions for each terminal on the circuit board.

Software Revision Number

Wiring to Hydrowire and Hydrosense Probes

Sounder Circuit Wiring

Connection to Remote Control Terminals

Aux 24 V DC Supply

Connection to Relay Contacts

Relay Types and Functions

Details on fault, local alarm, and main alarm relay operations.

Connection to Repeater Panels

Connection to Ancillary Boards

Panel Operation

Operational States and Indicators

Description of normal, alarm, and fault conditions, including LED indicators.

System Disablements

Procedures for disabling zones and sounders, and their functions.

Test Mode

Configuration Options

Reset Procedures

Internal Indications - Troubleshooting

18.1 Mains Fail

Indication of a mains power failure and troubleshooting steps.

18.2 Batt Fail

Troubleshooting battery connection and charging circuit faults.

Other Internal Faults

Details on CPU, power, earth, sounder, and communication faults.

Power Supply

Maintenance

Zone Designation Label

Hydrowire Commissioning Details

22.1 Installation

Steps for correctly installing Hydrowire cable and connection boxes.

22.2 Connection to Control Panel

Procedure for connecting Hydrowire to the main control panel terminals.

22.3 Remote Lamp Connection

How to connect a remote lamp indicator to the Hydrowire system.

22.4 Testing

Methods for testing the Hydrowire system after installation.

22.5 General Checklist

Important points to check for Hydrowire installation and operation.

Hydrosense Probe Commissioning

Overview

The Hydrosense HSCP is a conventional water detection control panel designed for use with the Hydrowire system and Hydrosense probes. It is available in 2, 4, and 8 zone configurations, offering a comprehensive solution for monitoring and signaling water detection events. The panel includes an integral, mains-powered battery charger and power supply, ensuring continuous operation even during power outages. It also features voltage-free relay contacts for both general alarm and local alarm conditions, which activate upon water detection, allowing for local control and signaling to other systems.

Usage Features:

The control panel's fascia incorporates standard silence and reset controls, along with two seven-segment LED displays and MODE, SELECT, and ENTER buttons. These controls facilitate easy entry and storage of codes for configuring the panel to meet specific installation requirements.

Under normal operating conditions, only the green "Power On" LED is illuminated. When a water detector activates, the "Common Alarm" indicator lights up, and the zonal "Alarm" indicators flash at approximately 2Hz. Both the alarm and local alarm relays will operate, signaling connected systems. Any sounders connected to the circuits will activate in common, zonal, or two-stage mode, depending on the selected configuration options.

To silence sounders, the "Enable Control" key must be inserted, and the "Silence/Sound alarm" button pressed. Once silenced, the "Zone Alarm" LEDs will change from flashing to a steady state. Pressing the "Silence/Sound alarm" button again will reactivate the sounders, allowing them to be toggled on and off as needed. To reset the panel, the "Enable Control" key is inserted, and the "Reset" button is pressed.

In the event of a zone fault, such as the removal of a water detector or wiring issue, the "Fault" LED and corresponding "Zone Fault" LEDs will illuminate. Similarly, a fault in the sounder circuit wiring will cause the "Fault" and "Sounder Fault" LEDs to light up. A power fault, indicated by the "Fault" and "Power Fault" LEDs, signifies a mains power failure, battery disconnection, or a high impedance in the charging circuit. The "System Fault" LED will light if the configuration memory is not set or becomes corrupt.

All LED indicators can be tested by pressing the "Lamp Test" button, without needing the "Enable Control" key. The buzzer can also be silenced at any time by pressing the "Buzzer Silence" button.

The system allows for the disablement of specific parts, which can be useful during maintenance or when works in a building might trigger false alarms. To disable zones, the "Enable Control" key is inserted, and the "Mode" button is pressed until "d" appears on the LED display. The "Select" button is then used to choose the zone number, and "Enter" confirms the disablement. The "Disable" LED and the "Zone Fault" LED for the disabled zone will light. Sounder outputs can be disabled by pressing the "Mode" button to select "db" on the display, then pressing "Enter," which will illuminate the "Disable" and "Sounder Fault" LEDs.

Delays can be activated on zones as configured in options 31 to 48. Pressing the "Mode" button until "Ad" appears on the display, then "Enter," will apply the set alarm output delays to the designated zones. The fault relay can also be disabled via configuration option 22.

The Hydrosense HSCP panels feature a single-handed test mode. With the "Enable Control" key inserted, pressing the "Mode" button until "t" appears, then selecting the desired zone with the "Select" button and confirming with "Enter," will activate test mode. In this mode, water detector activations are automatically reset after a few seconds (once the detector dries), eliminating the need to return to the control panel for resets. Disablements and zone tests are cleared by repeating the selection sequence, which toggles the function on or off.

Configuration options, accessible at access level 3, allow for customization of the panel's operation. To access this level, the "Write Enable" switch (located behind the panel plate) must be slid to the right. The panel buzzer will "pip" three times every few seconds as an indication of access level 3. Configuration codes are entered using the "Mode" and "Select" buttons for tens and units, respectively, and confirmed with "Enter." A flashing dot on the units display indicates a set option. Previously set options can be reviewed by scrolling through the codes; those with a flashing dot are active.

Maintenance Features:

The Hydrosense HSCP control panels require minimal specific maintenance. If the panel becomes dirty, it can be wiped with a damp, lint-free cloth and then dried. Detergents or solvents should not be used, and care must be taken to prevent water from entering the enclosure.

The control panel contains sealed lead-acid batteries for standby power during mains failures. These batteries typically have a life expectancy of about four years and should be tested annually according to the manufacturer's recommendations to ensure their continued suitability for standby applications.

Routine testing of the Hydrosense Water Detection System helps identify any malfunctions of the control panel, which should be reported to the alarm maintenance company immediately. If the control panel becomes faulty, the complete electronic assembly can be replaced. Before replacement, any configured options should be noted, and both mains and battery power must be removed. Field wiring should be carefully labeled and disconnected from the terminals. The PCB can then be removed by undoing the two screws holding the plate in position. Installation of a new PCB is the reverse of this procedure.

Internal indicators are provided for troubleshooting fault conditions not detailed on the front panel. These include:

  • Mains fail: Indicates no 230V AC supply, with the system running on standby batteries. If there's no power cut, the panel's mains fuse should be checked.
  • Batt fail: Indicates a disconnected standby battery, high resistance in the charging circuit, or a failed charging circuit. Batteries should be checked for connection and linkage, and the battery charger leads should be tested for 28 Volts.
  • CPU fault: Indicates the central processor unit failed to execute code correctly and was restarted by the system watchdog. The watchdog reset switch must be pressed to clear this fault. If the system doesn't return to normal, the circuit board may be damaged and require replacement.
  • Aux 24V fault: Indicates the electronic self-resetting fuse protecting the ROV output has operated due to an exceeded rating. The supply will resume once the fault condition is removed.
  • Batt low: Illuminates when the system runs on batteries, and the battery voltage is below 21V +/-2%.
  • Earth fault: Indicates a part of the system wiring is connected to earth. Wiring should be removed and reconnected one at a time to identify the faulty cable.
  • Sys fuse fault: Indicates the total power rating of the power supply has been exceeded, and the system fuse has operated. Loads should be reviewed and reconnected one at a time to identify the troublesome circuit.
  • S1 fault and S2 fault: Indicates a short or open circuit on sounder outputs. Wiring should be removed, end-of-line resistors refitted, and sounder circuit wiring checked.
  • Comms fault: Indicates communication loss with a repeater panel or ancillary board. Comms faults should be checked at all repeaters and ancillary boards to identify the source.

The panel's power supply requires a 230V AC supply, connected to a fused terminal block containing a 20mm, F1.6A L250V fuse, which should only be replaced with a similar type. The output voltage is 28V DC +/- 2V, with a total current rating of 3 Amps, including a maximum of 0.7A for battery charging. Fuse F12 on the circuit board is a self-resetting electronic fuse rated at 4 Amps. Mains wiring should be routed at least 50mm away from other low-voltage wiring and securely bonded to the building earth. Battery leads are supplied wired to the PCB, with a link to connect the two batteries in series. The PCB is fitted with a 20mm, 3.15A T1 glass fuse (F13) in the battery charging circuit, which must only be replaced with the same type. Correct battery polarity is crucial to prevent damage to the control panel.

A zone designation label is provided for writing text descriptions of each zone, facilitating easier identification of abnormal conditions.

For Hydrowire commissioning, lengths should be laid on the floor in protected areas, with no more than 2 meters between Hydrowires. For localized protection, distances may be greater. The cable should remain in contact with the floor, possibly using P clips. While sturdy, the cable can be damaged by crushing or excessive bending; a bend radius of 150mm is recommended. The Hydrowire must be terminated with an end-of-line plug (K2110). The terminating connection box (K2106) should be secured to the wall or floor to prevent stretching or pulling of the Hydrowire. The installed Hydrowire system should include a K2106 connection box, Hydrowire cable (K2104 or/and K2105), and an end-of-line plug unit (K2110). A red warning label should be clearly visible. Hydrowire should not contact surfaces above 70°C, and lengths greater than 50 meters are not allowed.

For connection to the control panel, the + and - terminals inside the connection box must be connected to the Z+ and Z terminals at the control panel. End-of-line resistors at the control panel should be discarded. It is advisable to leave the connection box lid off until all testing is complete.

A K2103 remote lamp unit can be wired to the - and rem. terminals in the K2106 connection box to identify the water detection area, especially in floor voids. Only one remote lamp unit should be connected per connection box.

Testing of Hydrowire is best done by dipping a thumb and forefinger into tap water, shaking off excess drips, and gripping the Hydrowire firmly while rolling it slowly. This should produce an immediate indication at the control panel. Over-wetting should be avoided to prevent long drying times.

General Hydrowire checklist points include avoiding excessive wetting, observing polarity, keeping lengths short to minimize electrical noise, avoiding installation near other cables, not twisting, bending sharply, stretching, standing on, or crushing the Hydrowire, avoiding exposure to surface temperatures above 70°C, and using only recommended Hydrowire system components.

Hydrosense Probe commissioning is best achieved by dipping the probe pins into a cup of tap water. This should immediately trigger a reaction at the control panel, the LED on top of the probe, and any fitted remote lamp unit or sounder.

Vimpex Hydrosense HSCP Specifications

General IconGeneral
TypeControl Panel
ModelHSCP
Enclosure RatingIP65
Weight2.5kg
Outputs4 relay outputs
Humidity Range0 to 95% RH, non-condensing
CommunicationRS485
Power Supply230V AC
Inputs8 digital inputs