Manual VIPA System 200V Chapter 4 Analog input/output modules
HB97E - SM-AIO - Rev. 12/32 4-7
The assignment of a function-no. to a certain channel happens during
parameterization. The function-no. 00h does not influence the function-no.
stored in the permanent parameterization data.
By entering FFh you may deactivate the concerning channel.
The following tables list all functions that are supported by the depending
channel.
Note!
When exceeding the overdrive region, the value 7FFFh (32767) is thrown,
at underrun of the underdrive region the value is 8000h (-32768).
Input range (channel 0, channel 1)
No. Function Measuring range / representation
00h Does not affect permanently stored configuration data.
3Bh
Voltage ±10V
Siemens S5 format
(two’s complement)
±12.5V /
12.5V = End overdrive region (20480)
-10...10V = nominal range (-16384...16384)
-12.5V = End underdrive region (-20480)
2Bh
Voltage ±10V
Siemens S5 format
(value and sign)
±12.5V /
12.5V = End overdrive region (20480)
-10...10V = nominal range (-16384...16384)
-12.5V = End underdrive region (-20480)
72h Voltage 1...5V
Siemens S5 format
(value and sign)
0...6V
6V = End overdrive region (20480)
1...5V = nominal range (0...16384)
0V = End underdrive region (-4096)
75h Voltage 0...10V
Siemens S5 format
(value and sign)
0...12.5V
12.5V = End overdrive region (20480)
0...10V = nominal range (0...16384)
no underdrive region available
28h
Voltage ±10V
Siemens S7 format
(two’s complement)
±11.76V /
11.76V= End overdrive region (32511)
-10...10V= nominal range (-27648...27648)
-11.76V= End underdrive region (-32512)
7Ah Voltage 1...5V
Siemens S7 format
(two’s complement)
0...5.704V
5.704V = End overdrive region (32511)
1...5V = nominal range (0...27648)
0V = End underdrive region (-6912)
continued ...