EasyManua.ls Logo

VIPA SM 231 - Page 128

Default Icon
178 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 4 Analog input/output modules Manual VIPA System 200V
4-22 HB97E - SM-AIO - Rev. 12/32
Input range (channel 3)
No. Function Measuring range / representation Conn.
00h Does not affect permanently stored configuration data.
01h Pt100 in 2wire mode
-200 .. +850°C /
in units of 1/10°C, two’s complement
(1, 2)
02h Pt1000 in 2wire mode
-200 .. +500°C /
in units of 1/10°C, two’s complement
(1, 2)
03h NI100 in 2wire mode
-50 .. +250°C /
in units of 1/10°C, two’s complement
(1, 2)
04h NI1000 in 2wire mode
-50 .. +250°C /
in units of 1/10°C, two’s complement
(1, 2)
06h Resistance measurement
600Ohm 2wire
- /
600 = Limit value (32767)
(1, 2)
07h Resistance measurement
3000Ohm 2wire
- /
3000 = Limit value (32767)
(1, 2)
FFh Channel not active (turned off)
Output range (channel 4, channel 5)
No. Function Output range
00h Does not affect permanently stored configuration data
09h
Voltage ±10V
Siemens S7 format
(two’s complement)
±11.76V
11.76V= End overdrive region (32511)
-10V...10V = nominal range (-27648...27648)
-11.76 = End underdrive region (-32512)
0Ah Voltage 1...5V
Siemens S7 format
(two’s complement)
0...5.704V
5.704V = End overdrive region (32511)
1...5V = nominal range (0...27648)
0V = End underdrive region (-6912)
0Dh Voltage 0...10V
Siemens S7 format
(two’s complement)
0...11.76V
11.76V= End overdrive region (32511)
0...10V = nominal range (0...27648)
no underdrive region available
0Bh
Current ±20mA
Siemens S7 format
(two’s complement)
±23.52mA
23.52mA = End overdrive region (32511)
-20...20mA = nominal range (-27648...27648)
-23.52mA = End underdrive region (-32512)
0Ch Current 4...20mA
Siemens S7 format
(two’s complement)
0...22.81mA
22.81mA = End overdrive region (32511)
4...20mA = nominal range (0...27648)
0mA = End underdrive region (-6912)
0Eh Current 0...20mA
Siemens S7 format
(two’s complement)
0...23.52mA
23.52mA = End overdrive region (32511)
0...20mA = nominal range (0...27648)
no underdrive region available
FFh Channel not active (turned off)
Note!
When exceeding the predefined range, 0V res. 0A is shown as value!