Manual VIPA System 200V Chapter 2 Analog input modules
HB97E - SM-AIO - Rev. 12/32 2-41
You may configure the channels in groups of two individually. 10byte are
available for the configuration data. Configuration parameters are stored in
permanent memory and they will be retained even if power is turned off.
The following table shows the structure of the parameter area:
Parameter area:
Byte Bit 7 ... Bit 0 Default
0 Diagnostic interrupt byte:
Bit 0: 0: wire break recognition channel 0/1 off
1: wire break recognition channel 0/1 on
Bit 1: 0: wire break recognition channel 2/3 off
1: wire break recognition channel 2/3 on
Bit 2: 0: wire break recognition channel 4/5 off
1: wire break recognition channel 4/5 on
Bit 3: 0: wire break recognition channel 6/7 off
1: wire break recognition channel 6/7 on
Bit 4, 5: reserved
Bit 6: 0: diagnostic interrupt inhibited
1: diagnostic interrupt enabled
Bit 7: reserved
0Fh
1 reserved 00h
2 Function-no. channel 0/1 (see table) 26h
3 Function-no. channel 2/3 (see table) 26h
4 Function-no. channel 4/5 (see table) 26h
5 Function-no. channel 6/7 (see table) 26h
6 Option Byte channel 0/1 00h
7 Option Byte channel 2/3 00h
8 Option Byte channel 4/5 00h
9 Option Byte channel 6/7 00h
Parameter data