2  D-302151 MCT-426, MCT-427 Installation Instructions 
3.2 Audible and Visual Indications 
The dual color LED and buzzer are used to signal various alarm and 
trouble messages as shown in Table 1 below: 
Table 1. Visual and Audible Indications 
Condition
 
Visual Indication (LEDs)  Audio 
Indication 
Red  Yellow 
Smoke alarm  Flash every 
500ms 
 
-  3 long beeps every 
4 sec. 
Heat alarm(***)  Flash every 
500ms
 
-  Long beep every 
2 sec. 
Tamper 
alarm(*)
 
-  -  Long beep every 
2 sec. 
Standby   Flash every 30 
sec.
 
-  - 
Low battery  Flash every 30 
sec.
 
-  Short beep every 
30 sec. 
Smoke sensor 
trouble
 
Flash every 60 
sec.
 
3 Flashes every 
60 sec.
 
Short beep every 
60 sec. 
Low sensitivity 
alarm
 
Flash every 30 
sec.(**)
 
-  Short beep every 
30 sec. 
Heat sensor 
trouble(***)
 
Flash every 60 
sec.
 
5 Flashes every 
60 sec.
 
Short beep every 
60 sec. 
Need to clean  2 flashes every 
30 sec.
 
-  2 short beeps 
every 30 sec. 
Test  See par. 3.7 
*  The tamper alarm will mute for 3 minutes at first power on, and 
will revert to normal mode when the tamper switch condition is 
changed. 
**  Delay of 15 sec. between buzzer beep and LED operation 
***   MCT-427 only 
3.3 Battery Connection and Initial Test 
Attention: The detector battery cover is fitted with a red button that 
prevents the detector from locking onto bracket if there is no battery 
inside.  
The smoke detector is supplied with a 3V CR123A / CR17450 battery. 
Battery connection for both types of batteries is illustrated in Figure 3a 
and 3b below. 
Battery cover
Open battery cover and
connect the battery to its
terminals (without
insulator). Verify proper
polarity.
3 volts CR123A
Tampe r
switch
Transmission
LED ON/OFF
button
 
Figure 3a. Battery Connection for CR123A  
Battery cover
Open battery cover and connect the battery to its terminals.
3 volts CR17450
Tamper
switch
Transmission
LED ON/OFF
button
 
Figure 3b. Battery Connection for CR17450 
Note: When the battery first makes contact, the alarm horn may 
sound for one second. This indicates that the battery is connected 
properly.  
Close the cover, then press the test button (see fig. 1) for about 5 
seconds, (for further details see par. 3.6). 
3.4 Resetting the Transmitter Module 
and Enrolling its PowerCode ID 
The detector has a wall / rear tamper switch to alert removal of 
detector. The tamper switch actuator, extending through a hole in the 
base (see Figure 3), is pressed against the bracket when the unit is 
attached to the bracket. 
Removal of the unit from the bracket will cause the switch contacts to 
open, creating a tamper event, which will be reported by the transmitter 
to the control panel.   
Refer to the control panel’s installation instructions and follow the 
procedure given there for enrolling transmitter IDs in the control panel's 
memory.  
When required to initiate a transmission for enrollment, press the smoke 
detector’s test button (see fig. 1) until the built-in horn sounds, or press 
the tamper switch. 
Note: It is much easier to carry out this operation while holding the 
MCT-426 / MCT-427 in your hand, close to the control panel.