7 minutes later, the compressor running frequency will be controlled as below:
3.5
3.0
2.5
2.0
1.5
1.0
0.5
-0.5
-1.0
A
B
C
D
E
F
G
H
While
Temp.zone A B C D E F G
Frequency F8 F8 F7 F6 F5 F3 F1
Note:
When T1-Ts keeps in the same temp.zone for 3 minutes, the compressor will run as the below rules:
A~E: Increase the frequency to the higher level until to F8.
F: Keep the current frequency.
G: Decrease the frequency to the lower level until to F1.
H: Run at F1 for 1h.(if T1-Ts<-2, compressor will stop)℃
Meanwhile, the compressor running frequency is limited by the current.
I3COOL
I2COOL
Off
Decrease
Hold
Resume
I1COOL
Off: Compressor stops.
Decrease: Decrease the running frequency to the lower level.
Hold:Keep the current frequency.
Resume:No limitation for frequency.