8.4.5.3 Room overlow temperature protection
In drying mode, if room temperature is lower than 10, the compressor will stop and not resume until ℃
room temperature exceeds 12.℃
8.4.5.4 Evaporator anti-freezing protection, condenser high temperature protection and outdoor unit
frequency limit are active and the same as that in cooling mode.
8.4.5.5 The outdoor fan operates the same as in cooling mode.
8.4.6 Forced operation function
8.4.6.1Enter forced operation function:
When the machine is off, pressing the touch button will carry the machine to forced auto mode, after
this, if pressing the button once again within 5 seconds, the machine will turn into forced cooling mode.
In forced auto, forced cooling or any other operation mode, pressing touch button will turn off the
machine.
8.4.6.2 In forced operation mode, all general protections and remote control are available.
8.4.6.3 Operation rules:
Forced cooling mode:
The compressor runs at F2 frequency and indoor fan runs as breeze.After running for 30 minutes. the
machine will turn to auto mode as 24℃ setting temperature.
Forced auto mode:
The action of forced auto mode is the same as normal auto mode with 24 setting temperature.℃
8.4.7 Timer function
8.4.7.1 Timing range is 24 hours.
8.4.7.2 Timer on. After turning off, the machine will turn on automatically when reaching the setting
time.
8.4.7.3 Timer off. After turning on, the machine will turn off automatically when reaching the setting
time.
8.4.7.4 Timer on/off. After turning off, the machine will turn on automatically when reaching the
setting “on” time, and then turn off automatically when reaching the setting “off” time.
8.4.7.5 Timer off/on. After turning on, the machine will turn off automatically when reaching the
setting “off” time, and then turn on automatically when reaching the setting “on” time.
8.4.7.6 The setting time is relative time.
8.4.7.7 The tolerance of timer is 1 minute per hour.