TITANUS RACK·SENS
®
1U Installation Pipe System
TRS_A_06-en-e Data: 03/09 6 – 1
6 Installation of the Pipe System
The pipes and fittings used for the pipe system must always meet re-
quirements for Class 1131 in accordance with EN 61386-1, 2004.
Class 1131 puts the following requirements on the pipe system used:
characteristics severity code
compression resistance 125 N
impingement resistance 0,5 kg, drop height at 100 mm
temperature range -15 °C to +60 °C
In principle, the following pipes as well as the related fittings are to be
used in configuring the pipe system:
external diameter internal diameter
ABS PVC
air sampling pipe 25 mm 21,4 mm 21,2 mm
Take note of the temperature range specified in the “Technical data”
chapter under “3.3 Pipe system” when configuring the pipe system.