Table 10 Pump Parameters
Parameter
Name
Range
Default
Description
P01
Running Mode
0/1/2
0
Selects the operating mode of the pump,
0 for normal, 1 for special, 2 for interval
P02
Running Interval
Time
0~120min
30min
Time between pump operating cycle
when the compressor is off
P03
Running Duration
0~30min
3min
Pump operating cycle time when the
compressor is off
P04
Advanced Start
Time
0~30min
1min
Time the pump must run for before the
compressor will start
P05
Manual
Control
0/1
0
Disables (0) or enables (1) manual pump
control
* Indicates that this parameter is not adjustable
Table 11 Fan Parameters
Parameter
Name
Range
Default
Description
F01
Max Speed in
Heating
*
1050r
Maximum fan speed in Heating Mode
F02
Min Speed in
Heating
*
300r
Minimum fan speed in Heating Mode
F03
LP of Suction for
Heating
*
4bar
Low pressure limit of suction line for
heating at maximum fan speed
F04
HP of Suction for
Heating
*
11bar
High pressure limit of suction line for
heating at minimum fan speed
F05
Max Speed in
Cooling
*
1050r
Maximum fan speed in Cooling Mode
F06
Min Speed in
Cooling
*
300r
Minimum fan speed in Cooling Mode
F07
HP of Exhaust for
Heating
*
33bar
High pressure limit of discharge line for
heating at maximum fan speed
F08
LP of Exhaust for
Heating
*
15bar
Low pressure limit of discharge line for
heating at minimum fan speed
F09
Manual Fan
Speed
0~2000r
0r
If set (greater than 0) the fan will run
constantly at this speed when on
F10
Timer Mute
0/1
0
Enable reduced fan speed (0 for No, 1
for Yes)
F11
Mute Timer Start
Hour
0~23h
0h
Start time for mute (reduced fan speed)
mode
F12
Mute Timer End
Hour
0~23h
0h
End time for mute (reduced fan speed)
mode