EasyManua.ls Logo

Watlow 942 Series - Setup; Setup Menu Parameters and Descriptions

Watlow 942 Series
63 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Setup, Chapter 4 WATLOW Series 942 User's Manual
27
Setup
Use this page as a master copy for configuring your Series 942.
Do not enter any values here; make photocopies instead.
Setup Parameters Value Range Factory Default
LOC 0 to 3 0
In J, K (appears as H), t, n, c, r, S, b, J or r
Pt2, rtd1, rtd.1, 0-5, 420
Dependent on model number.
dEC 0, 0.0, or 0.00 0
Dependent on input type.
C _ F C or F F
Will not appear if In = 0-5 or 420.
rL rL to rH Input selection dependent.
rH rH to rL Input selection dependent.
Ot1 ht or CL ht
HYS1 1°F - 999°F, 1°C - 540°C, 1U - 999U 3°F
0.1°F - 99.9°F, 0.1°C - 54.0°C, 0.1U - 99.9U
Ot2 ht, CL or no CL
HYS2 1°F - 999°F, 1°C - 540°C, 1U - 999U 3°F
0.1°F - 99.9°F, 0.1°C - 54.0°C, 0.1U - 99.9U
Ot3 AL, Ent or no AL
AL1 Pr or dE Pr
LAt 1 LAt or nLA nLA
Dependent on AL 1 = Pr or dE.
HYS3 1°F - 999°F, 1°C - 540°C, 1U - 999U 3°F
0.1°F - 99.9°F, 0.1°C - 54.0°C, 0.1U - 99.9U
SIL On or OFF OFF
Ot4 AL, Ent, no, PrOC or StPt AL or PrOC
AL 2 Pr or dE Pr
LAt 2 LAt or nLA nLA
HYS4 1°F - 999°F, 1°C - 540°C, 1U - 999U 3°F
0.1°F - 99.9°F, 0.1°C - 54.0°C, 0.1U - 99.9U
rtd JIS or din din
PtYP ti or rAtE ti
gSd 0 - 99°F, 0 - 55°C, 0 - 99U 0
0.0 - 9.9°F, 0.0 - 5.5°C, 0.0U - 9.9U
POUt Cont, HOLd, Abrt or rSET Cont
PStr Proc or StPt StPt
bAUd 300, 600, 1200, 2400, 4800, 9600 1200
dAtA 7 o = Odd parity, 7 E = Even parity 7 o
8 n = 8 data bits and no parity
Prot FULL or On FULL
Addr 0 to 31 0
Log On or OFF OFF
Int 0.0 to 60.0 minutes 0.0
tag PSA, PS-, P-A, P--, -SA, ---
-S-, --A, ---
P = Process, S = Set point
A = Auxiliary Status
Table 2 -
Setup Menu Parametersand Descriptions.