Programming, Chapter 5
WATLOW Series 942 User's Manual 37
Figure 37 -
Guaranteed Soak
Deviation Example
Jumploop
Time
Guaranteed Soak
Deviation Window
Around Set Point
Set Point
Set Point
Multiple Profiles
The Series 942 is a single profile control, but can be programmed for multiple
profiles. To do this, enter your first profile; the next step you enter following the
End step is the start of another profile. You can continue entering profiles until you
run out of steps, remember there are a total of 24 steps.
Jumploop
The Series 942 can only jump backwards. A jump forces you to a step already
performed. The Jump Step (JS) must be less than the current step. You cannot
jumploop to the step that you are on.
Step 2 StPt
Step 3 StPt
Step 4 StPt
Step 5 Jumploop JS - 02 JC - 01
Step 6 End
Your Jump Count (JC) can be anything from 0 - 100. If you enter 0, this will be an
infinite loop and never progresses to Step 6.