SmartSensor HD
15
25 A per conductor
Both communication and power conductors can be bundled together in the same cable as long as the above-mentioned
conditions are met.
2.4 Lightning Surge Protection. e RVSD shall be installed using lightning surge protection on all communication and
power lines. e surge protection devices shall meet or exceed the EN 61000-4-5 Class 4 specications. e lightning
surge protection unit shall be the Wavetronix Click 200 or equivalent. e lightning surge protection unit supplied shall be
physically compatible with the cable provided.
2.5 Power Supply. e RVSD shall be installed using the Click 201, Click 202 or an equivalent AC to DC power con-
verter that meets the following specications:
e power converter shall be power rated at 15 W or greater at 77°F (25°C) and 10 W or greater at 165.2°F (74°C).
e power converter shall operate in the temperature range of to -29.2°F to 165.2°F (-34°C to 74°C).
e power converter shall operate in the humidity range of 5% to 95% at 77°F (25°C) non-condensing.
e power converter shall accept an input voltage of 85 to 264 VAC or 120 to 370 VDC.
e power converter shall operate at an input frequency of 47 Hz to 63 Hz.
e power converter shall produce an output voltage of 24 VDC ±4%.
e power converter shall have a hold-up time of greater than 20 ms at 120 VAC.
e power converter shall withstand a voltage across its input and output of 2 kV. e power converter shall withstand a
voltage across its input and ground of 1.5 kV.
e power converter shall comform to safety standards UL 60950 and EN 60950.
e power converter shall conform to EMC standards EN 55022 Class B and EN 61000-3-2, 3.
In brown-out conditions (i.e. < 85 VAC input), the output voltage of the power converter shall be less than 1 VDC.
2.6 Input File Cards. If input le cards are used in the detection system, then the Click 112, Click 114 or an equivalent
that meets the following specications shall be used.
e input le cards shall be compatible with 170, 2070, NEMA TS 1, and NEMA TS 2 style input racks.
e input le card shall translate data packets from the RVSD into contact closure outputs.
e input le card shall support dual loop (speed trap) emulation, as well as the following modes of operation:
Pulse (a single 125 ms output pulse for each vehicle)
Presence (an output pulse corresponding to the duration of each vehicle in the detection zone)
Actuation (true presence output in real time)
Single loop speed (duration of the pulse is inversely proportional to the speed of the vehicle)
e input le card shall receive data packets over an RS-485 bus at any of the following baud rates: 9600, 19200, 38400
and 57600 bps.
e input le card shall autobaud and auto-detect an RVSD over wired and wireless communication channels that have a
maximum latency of 500 ms.
e input le card shall comply with the NEMA TS 2-1998 Trac Controller Assemblies with NTCIP Requirements