EasyManua.ls Logo

wavin DRT-200 - 8.7 Readable, writeable register variables

Default Icon
48 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
W
avin Tempower Control Manual
Wavin Tempower Control
Heating and Cooling systems
.
W
avin Tempower Control Manual
Wavin Tempower Control
Heating and Cooling systems
.
37
8
8
.
.
7
7
R
R
e
e
a
a
d
d
a
a
b
b
l
l
e
e
,
,
w
w
r
r
i
i
t
t
e
e
a
a
b
b
l
l
e
e
r
r
e
e
g
g
i
i
s
s
t
t
e
e
r
r
v
v
a
a
r
r
i
i
a
a
b
b
l
l
e
e
s
s
Address Description [unit] Value
4178 TH1 cooling set point [0.1 °C] 100..500
4179 TH1 heating set point [0.1 °C] 100..500
4180 TH1 economy set point [0.1 °C] 50..500
4181 TH2 cooling set point [0.1 °C] 100..500
4182 TH2 heating set point [0.1 °C] 100..500
4183 TH2 economy set point [0.1 °C] 50..500
4184 TH3 cooling set point [0.1 °C] 100..500
4185 TH3 heating set point [0.1 °C] 100..500
4186 TH3 economy set point [0.1 °C] 50..500
4187 TH4 cooling set point [0.1 °C] 100..500
4188 TH4 heating set point [0.1 °C] 100..500
4189 TH4 economy set point [0.1 °C] 50..500
4190 TH5 cooling set point [0.1 °C] 100..500
4191 TH5 heating set point [0.1 °C] 100..500
4192 TH5 economy set point [0.1 °C] 50..500
4193 TH6 cooling set point [0.1 °C] 100..500
4194 TH6 heating set point [0.1 °C] 100..500
4195 TH6 economy set point [0.1 °C] 50..500
4196 TH7 cooling set point [0.1 °C] 100..500
4197 TH7 heating set point [0.1 °C] 100..500
4198 TH7 economy set point [0.1 °C] 50..500
N
N
o
o
t
t
e
e
s
s
The BMS can continously write the set point
variables. If not receive any news values then it
will work according to the last status. The WTC
will start with the default values after connecting
to the power
. The default values can be set by