avin Tempower Control Manual
Wavin Tempower Control
Heating and Cooling systems
.
avin Tempower Control Manual
Wavin Tempower Control
Heating and Cooling systems
.
41
D
esign Manual
TELEPHONE
+31 (38) 4294911
4
E-MAIL
info@wavin.com
www.wavin.com
P
P
r
r
o
o
b
b
l
l
e
e
m
m
WTC3 is not working
(Power LED is not lighting)
DRT200 are not respond
(neither of LED has activity)
D
RT200 is not respond for any
touch but the LEDs are lighting
Can not change the
heating/cooling mode at the
master DRT-200
Can not change the economy
mode to comfort mode at the
DRT-200
Can not turn ON the DRT-200
In case of H/C change over the
valves are not react immediatelly.
The control LED is fleshing on
WTC-3
A WTC3 detecting condensation,
while the surface of dew point
sensor is dry . (Yellow LED is
lighting on WTC-3)
The sign of dew point sensor not
the right actuator is close the
circuit
C
C
a
a
u
u
s
s
e
e
The unit is no get any
voltage
No connection between
WTC-3 and DRT-200
N
ot the right program
has been selected
The addressing of
DRT-200 is not
correct
Input for change over is not
selected properly
Needs to be configur
e
Needs to be configure
Change over is in
progress
Shortcut in the wire of
dew point sensor
The dew point sensor is not
connected to the right input
R
R
e
e
m
m
e
e
d
d
y
y
Check connection of electric
power at plug 1 and 2 with
measurement unit
Check the connection between
the 46-47 plug of WTC-3 and
3-4plug of DRT-200 (polarity,
demage, shortcut).
Reversed polarity NOT allowed!
C
heck the program setting on
program selector at back side of
WTC-3
Set the proper address for every
DRT-200 (1..7). check the status of
every connected DRT-200 via
configuration program
According to the factory default the
master DRT-200 can change only
the H/C mode.
Check the settings of H/C change
over with configuration program
Check the settings of C/E change
over with configuration program
Check the settings of ON/OFF
change over with configuration
program
This is not a fault. WTC-3 is in
change over mode. Wait until the
delay is in progress (default: 10
minutes
Disconnect the dew point sensor.
The condensation sign must to
finish at WTC-3. Check the wire
for demage, brake or shortcut.
Check the connection. This could
happen only in case if the dew
point sensor are connected directly
to the WTC-3
1100.. TTrroouubblleesshhoooottiinngg