12/20/2017 TECH-533/ D.W.O. 22902 Page 13 of 20
4.4.7 Calibration Timeout (REG CAL or LONG CAL): Time for the first move in calibration will
be set at a maximum of 30 seconds for REG CAL and all subsequent time outs are keyed
off the time it takes to go from closed to open, to create much shorter subsequent time
outs for smaller valves. The initial 2 minute time out can be lengthened in the Manual
Calibration routine Long CAL.
This should normally be left at REG CAL. If however the valve is likely to take more than
30 seconds to open or close, switching to LONG CAL allows 100 seconds.
The LCD shows “TX FT LO or TX FT HI” press the SEL Key again and the LCD shows “REG
CAL or LONG CAL”. REG CAL or LONG CAL can now be selected.
Pressing the DOWN or UP Key toggles this setting.
4.4.8 Saving or discarding changes:
At the end of any procedure, changes can be kept by saving the changes. To Save the
changes by pressing and holding the Key until the LCD shows:
HOLD
TO SAVE
SAVED Changes made to this point are saved.
Releasing after a shorter time will cause the changes to be discarded.
LCD will show “DISCRDED”
Or you can Exit without saving, this discards the changes that were entered.
All Manual Calibration Steps will timeout after 2 minutes, discarding any changes if no
Key is pressed during that time.
4.4.9 Cancelling Calibration
When the LCD displays “AUTO CAL and you do not want to perform this operation. Do
nothing. Within 15 seconds the function displayed is canceled and the LCD display
reverts back to opening percentage “xx %”
If starting an Auto Calibration by mistake. Wait 5 seconds and press again. LCD
shows “CALIBRATION CANCELED”. The LCD display will revert to opening percentage
“xx %” after 20 seconds.
4.4.10 To reset to the Factory Default Settings
Press
SEL Key until the LCD scrolls “Restore Factory Default .
Press Down arrow until LCD reads “Hold Key”.
Press and hold Key.
LCD will scroll Factory Default Success”
Factory default settings are now enabled.