WIKA Operating instructions / Betriebsanleitung / Mode d'emploi PS-20, PS-21
Specifications Model PS-20 / PS-21
Damping ms 0 ... 500
Manufacturer‘s settings when selected via the software the manufacturer‘s values are activated
Switching time ms < 6
Insulation voltage VDC 500
Accuracy adjustment of switching
points
6)
% of span ≤ 0.5 (BFSL)
≤ 1.0
5)
5) Including non-linearity, hysteresis, zero point and full scale error (corresponds to
error of measurement per IEC 61298-2).
Adjusted in vertical mounting position with lower pressure connection.
6) In individual cases equipment exposed to strong electromagnetic fields with
frequencies up to 2.7 GHz may show increased measurement errors of up to 3 %.
To avoid such influences on the measurement signal do not operate the equipment
in proximity to strong transmitters or radio installations, or use suitable sheath
current filters.
Non-repeatability % of span ≤ 0.25
1-year stability % of span ≤ 0.2 (at reference conditions)
Permissible temperature ranges
Medium *) -30 … +100 °C {-40 … +125 °C} -22 ... +212 °F {-40 … +257 °F}
Ambient -20 ... +80 °C -4 ... +176 °F
Storage -40 ... +100 °C -40 ... +212 °F
Compensated temp. range 0 ... +80 °C +32 ... +176 °F
Temperature coefficients in
compensated temp. range
Mean TC of zero % of span ≤ 1.0
Mean TC of span % of span ≤ 1.0
CE- conformitiy
Pressure equipment directive
EMC directive
EN 61326 Emission (Group 1, Class B) and Immunity (industrial
locations)