25WIKA operating instructions pressure switch, model PSD-3x
EN
11430486.07 04/2015 EN/DE/FR/ES
6. Commissioning, operation
Menu (programming and factory setting)
Display mode
Long press on menu key
Programming mode
Factory setting:
SP1 / FH1 Value (Min: MBA +0.5 % Max: MBE) Instrument nominal pressure
RP1 / FL1 Value (Min: MBA Max: SP1 -0.5 %) Instrument nominal pressure -10 %
SP2 / FH2 Value (Min: MBA +0.5 % Max: MBE) Instrument nominal pressure
RP2 / FL2 Value (Min: MBA Max: SP2 -0.5 %) Instrument nominal pressure -10 %
EF RES Yes / No Reset to factory setting
DS1 Value 0 ... 50 s 0 s
DR1 Value 0 ... 50 s 0 s
DS2 Value 0 ... 50 s 0 s
DR2 Value 0 ... 50 s 0 s
OU1 PARA HNO, HNC, FNO, FNC HNO
OU2 PARA HNO, HNC, FNO, FNC HNO
UNIT Unit BAR, MPA, KPA, PSI, KG/cm
2
Order-related
0SET Yes / No
Zero point adjustment 3% of span
ACT, HIGH, LOW, OFF, SP1/FH1, RP1/
FL1, SP2/FH2, RP2/FL2
ACTDISM
PARA
DISU Value 1/2/5/10 update/second 5
DISR Yes / No Rotate display by 180°
RHL Yes / No Reset HIGH, LOW
PAS Value Password without
TAG Value Measuring point number without
Legend:
MBA = Start of measuring range
MBE = End of measuring range
END END