Model GL indirect-fired water heatersProduct Manual
Troubleshooting
(continued)
Water on the floor near the tank
1 Check for leaks from sources other than the water heater.
• Check for possible water seepage through foundation cracks. Did the water appear after a heavy rain?
2 Is the source of water from the T&P relief valve?
• Place a bucket under the discharge piping of the T&P relief valve and monitor it for a day or two. This is
a procedure that can be done by the homeowner.
• If the T&P relief valve is the source, refer to page 34 of this guide.
3 Loose piping connections?
• Check all connections – boiler connections, domestic connections, etc.
• Check all the boiler connections to the water heater.
• A build-up of corrosion is a sure sign of a leak.
• Excessive force or water hammer can damage the welds where the piping connections enter the water
heater tank.
• If water is leaking from around one of the tank connections, a weld may have been broken. Contact
your Williamson-Thermoflo supplier to determine how to handle the problem.
Top of tank or insulation wet
1 Check for leaks from sources other than the water heater
• Check for possible overhead pipes leaking onto the tank.
2 Loose piping connections?
• Check all connections – piping connections to the tank and elsewhere if the vicinity.
• Check around valve stems.
• A build-up of corrosion around a joint is a sure sign of a leak.