Chart I: Functions of potentiometers and hook switches (Fig. 2/3)
Switch/Pot. Functions
Potentiometer for FLC-settings:
P1 for No. 1 pump
P2 for No. 2 pump
P3 for No. 4 pump
P4 for No. 3 pump
P8 to set pump stop time delay (0 –2 min)
P9 to set pump stop time delay on low water cut-out (0 –2 min)
Setting pressure setpoints (see pump duty chart, Fig. 5)
p
max
2
P5 – base-load pump switch-off pressure
p
max
1
P6 – base-load pump switch-off pressure
pmin P7 – switch-on pressure for all pumps
S 1 Effect reversal for input low-water cut-out:
S 1 open: Plant runs on closed contacts on terminals WM,
plant stops on open contacts on terminals WM
S 1 closed: Reverse action.
S 2 Test run:
S 2 open: Test run activated
S 2 closed: Test run deactivated
S 5 Sensor input:
S 5 open: Plant stops on opening of sensor contacts (without fault signal)
S 5 closed: Plant runs on opening of sensor contacts (oll pumps)
S 3, 4, 7 Setting to the number of controlled pumps:
No. of pumps: Hook switch positions: S 3 S 4 S 7
1: 100
2: 010
3: 001
4: 000
0
open, 1
closed
Motor fuses, 6.3 diam. x 32 mm, 16 amps inert, 440 V
for pumps: Phases: L01L02L03
F1-3 P1 Fuses: F01F02F03
F4-6 P2 F04F05F06
F11-13 P3 F11 F12 F13
F14-16 P4 F14 F15 F16
F7 Control circuit fuse: 6,3 diam. x 32 mm, 0.1 mA, 250 V
Chart II: Settings of hook switches and potentiometers for different applications
Switch/Pot. Pressure boosting Fire services
S 5 *0* *1*
S 2 0 0
S 1 0 0
Set FLC value to motor name plates
22
0.5 0.5
* 0 open, 1 closed