Installation and operating instructions Wilo E.../1-5 8
English
5.3 Scope of delivery
Circulation pump complete
Installation and operating instructions
6 Description and function
The pump (fig. 1) consists of a hydraulic system, a glandless
pump motor an electronic control module. The control module
includes a red button for setting all parameters.
7 Installation and electrical connection
Installation and electrical connection must be carried out in
accordance with local regulations and only by qualified per-
sonnel!
WARNING! Risk of personal injury!
The existing directives for accident prevention must be
adhered to.
DANGER! Danger of electric shock!
Danger from electrical current must be eliminated.
Local directives or general directives [e.g. IEC, VDE etc.] and
local power supply companies must be adhered to.
5.2 Technical data
Connected voltage 1~230 V +10 %/-15 %, 50 Hz ±5 %
Protection class IP 44 (acc. fig. 3)
Water temperatures + 10°C to + 95°C
Max. operating pressure 10 bar
Max. ambient temperature + 60°C
Min. inlet pressure 0.05 bar at 50°C / 0.3 bar at 95°C