3. Installation
3-1. Mounting
3-2. Outside dimension & Panel cutting size
Caution : Maintenance and to ensure the safety of the device if you
add a space to more than 125min size is recommended.
4. Terminal diagram
4-1. Terminal wiring
4-2. A power source wiring
Caution
1. For an electric shock prevention to turn on electricity to the
machinery and tools which after one sees a protective ground
connection surely.
2. To the electric wire terminal to use the insulation sleeve compression
terminal.
3. The device's power supply voltage to match the voltage of the power
is in check.
4. For the protection of life to turn on an electric current to the
instrument after attaching the cover.
Attention
1. To all the member front line 600V vinyl insulation front lines (JIS
C3307), or to use the front line of above considerable width.
2. To the protective ground terminal to connect above of 3rd type(to
connect below earth resistance 100Ω and smallest size 1.6㎜).
3. Other protection devices and grounding, the grounding in public may
be affected by noise. Accordingly the public are advised not to other
devices.
5. Feature
High response
4point alarm & Dead band set
Isolation current output (DC 4.00~20.00mA)
6. General Specification
6-1. mA input : DC 4.00~20.00mA
Pulse input
Low level voltage : DC 0.7V or less
High level voltage : DC 1.5V or more
Max high voltage : DC 30V
Input resistance : 150kΩ
* Other input specifications must be ordered separately.
6-2. Measuring and display cycle : Minimum 1s.(more short according
to input frequence)
6-3. CMRR(Common Mode Rejection Ratio) : 140dB or more
6-4. NMRR(Normal Mode Rejection Ratio) : 60dB or more
6-5. Moving average filter by selection : None, Average 4, 8, 16,32
6-6. Built-in sensor power source : DC 12V 30mA ±0.5%
6-7. Accuracy : ±0.2% FS
6-8. Isolation current output(Option)
Current : DC 4.00~20.00mA
Maximum load resistance : 600Ω
Isolation resistance(Input-Output) : 100MΩ or more (DC 500V)
6-9. Isolation voltage output(Option)
Voltage : DC 0~10V
Minimum load resistance : 1kΩ or more
Insolation resistance(Input-Output) : 100MΩ or more(DC 500V)
6-10. Pulse output
Open collector output : Max 100Hz, DC 50V/within 30mA
Voltage output : Max 100Hz, Lo(DC 0V), Hi(DC 24V)
Relay contact output : Max 5Hz same as alarm
6-11. Ambient condition
Operation temperature & Humidity : -10~50℃, 10~90%
Storage temperature & Humidity : -20~70℃, 5~95%
6-12. Power supply
Voltage : asAC 85~265V(45~65Hz), DC 24V(Option)
Power consumption : Max 4VA
Isolation resistance : 100MΩ , DC 500V
(FG-Input, FG-Power, Power-Input, Input-Output)
6-13. Etc
Weight : 500g
Mounting : Panel mount
Dimension : 96(W) X 48(H) X 112(D)mm
7. Major Function
7-1. Display scaling function(mV, Volt, mA only)
This Function changes and sets the display value
according to scale and input range.
ex) In case of input range 0.00~10.00
Hz
and
Level 0.00~7.00t/m