Rectifying faults
Error E2
E2 flashing.
The flow temp. NTC sensor is damaged.
Check Action
1. B Activate menu option Show serv-
ice parameters.
B Select 0.1 Flow temp. sensor.
Is a temperature between 0 and
5˚C displayed?
yes: The heating outlet NTC sensor is in short circuit:
B Power OFF the appliance.
B Replace CH flow NTC sensor; observe fitting
instructions for NTC sensor when doing so.
B Turn ON the appliance.
E2? 2.
no: 2.
2. B Unplug 20-pin connector from
PCB.
B Check resistance from connec-
tions 8 to 9 on the cable side.
Does the value match the ones
described in table 7, page 50?
yes: B Make a note of the altered service function set-
tings (see table 1 on page 7) in order to keep the
altered values.
B Power OFF the appliance.
B Disconnect the boiler electrical connection.
B Change PCB control board.
B Reconnect the boiler electrical connection.
B Turn ON the appliance.
B Restore service settings previously noted down.
no: 3.
3. B Unplug NTC sensor from cable.
B Check resistance of NTC sensor.
Does the value match the ones
described in table 7, page 50?
yes: B Power OFF the appliance.
B Disconnect the boiler electrical connection.
B Change the 20-pin connector lead assembly.
B Reconnect the boiler electrical connection.
B Turn ON the appliance.
no: B Change NTC sensor.