27 
power is cut (No battery).   
※3.  The  serial  number  of  input  coil  and  output  relay  are  octal  data,  other  memorizers’ 
number are all decimal data. 
※4. There is no I/O point connected with exterior device can be used as interior relay. 
 
Soft component power failure area setting: 
XP1/XMP1: 
Soft 
component 
Area  Function  Default value
Power failure 
memory area 
D  FD8202 
First address of the power 
failure memory area of D 
100  D100~D149 
M  FD8203 
First address of the power 
failure memory area of M 
200  M200~M319 
T  FD8204 
First address of the power 
failure memory area of T 
640  No set 
C  FD8205 
First address of the power 
failure memory area of C 
320  C320~C631 
S  FD8206 
First address of the power 
failure memory area of S 
512  S0~S31 
 
XP2/XMP2: 
Soft 
component 
Area  Function    Default value
Power failure 
memory area 
D  FD8202 
First address of the power 
failure memory area of D 
4000  D4000~D4999 
M  FD8203 
First address of the power 
failure memory area of M 
3000  M3000~M7999
T  FD8204 
First address of the power 
failure memory area of T 
640  No set 
C  FD8205 
First address of the power 
failure memory area of C 
320  C320~C639 
S  FD8206 
First address of the power 
failure memory area of S 
512  S512~S1023 
 
XP3/XMP3: 
Soft 
component 
Area    Function    Default value
Power failure 
memory area 
D  FD8202 
First address of the power 
failure memory area of D 
4000  D4000~D7999 
M  FD8203 
First address of the power 
failure memory area of M 
3000  M3000~M7999
T  FD8204 
First address of the power 
failure memory area of T 
640  No set