EasyManuals Logo

XPower Easy Max User Manual

XPower Easy Max
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #44 background imageLoading...
Page #44 background image
- 44 -
5 oLP
Short circuit
protection
This code activates when the motor
suffers a short circuit. The value
detected must reach the limit
value for 5 microseconds
no
Restart the system
and wait 5 minutes
before restoring
electrical power.
6 oCP
Water over
pressure
protection
This code activates when
the pressure in the pipes is
above 99% of the maximum value
yes
automatic restore
when the pressure
drops below 95% of
the maximum value
7 oS
Pressure sensors
protection
This code activates when
the pressure sensor is not
connected or is damaged
yes
automatic restore
when the sensor
is connected or
replaced
8 oP
Disconnected
phase protection
This code activates when
there is a malfunction
in the three-phase current.
no
Maintenance and a
manual restore
is required
9 EAA Connection error
This code activates when there
is a connection error
no
Maintenance and
a manual restore is
required
check the
cables
Protection functions and description
GB

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the XPower Easy Max and is the answer not in the manual?

XPower Easy Max Specifications

General IconGeneral
BrandXPower
ModelEasy Max
CategoryWater Pump
LanguageEnglish