GAS-FIRED DOUBLE-EFFECT
ABSORPTION CHILLER-HEATER
This product is a gas-fired absorption unit which provides chilled water for cooling or
hot water for heating in central plant type air conditioning systems. Units with nominal
refrigeration capacities of 30, 40, 50, 60, 80, and 100 tons are complete with operating
and safety controls.
When this equipment is correctly applied, installed in accordance with Yazaki
INSTALLATION INSTRUCTIONS, and properly maintained, it can provide many years
of trouble-free operation.
CONTENTS
GENERAL Page
ABSORPTION PRINCIPLE 2
COOLING OPERATION 2
HEATING OPERATION 3
CONTROLS
GENERAL INFORMATION 4
CONTROL ADJUSTMENTS 6
OPERATION
COOLING 7
HEATING 7
SAFETY CONTROLS 7
REMOTE CONTROL 7
PRECAUTIONS 7
MAINTENANCE Page
GENERAL INFORMATION 8
ROUTINE MAINTENANCE 8
MAINTENANCE INTERVALS 8
EVACUATION OVERVIEW 8
CHEMICAL MAINTENANCE 9
WINTER SHUTDOWN 10
TROUBLESHOOTING 10
WATER QUALITY 11
ERROR CODES 11
STARTUP & MAINTENANCE
DATA SHEET 13
WARRANTY
YAZAKI LIMITED EXPRESS
WARRANTY 14
OPERATING INSTRUCTIONS
CH-K30, 40, 50, 60, 80, 100

Questions and Answers

  • K
    Kevin JimenezAug 2, 2025
    What to do if Yazaki CH-K30 Heater does not operate?
    • A
      Arthur DavisAug 2, 2025
      If the Yazaki Heater does not operate, there might be several reasons. First, check the LED for the Power indication on the Control Panel. If it is not illuminated, examine the main power disconnect, fuses, and breakers. Also, the solution pump might not be running. Check the THRP overload switch and the GP temperature. The solution pump may remain off until the GP temperature rises above 190°F (88°C). Finally, if the WTO temperature is above the set point, the unit may have shut down normally. To force operation, turn off power to the chiller-heater for 10 seconds, and then restore power. The chiller-heater should start up if the WTO sensor reading is above the set point.
  • L
    Lance ClarkAug 22, 2025
    What to do if Yazaki CH-K30 is not running but WTO temperature is above set point?
    • M
      Michael JohnsonAug 22, 2025
      If the Yazaki Heater is not running but the WTO temperature is above set point, it may not indicate a problem. If the chilled water loop has reached the desired set point, the unit will shut down until the WTO sensor reads a temperature 3.6°F (2°C) above the set point temperature. To force operation, turn off power to the chiller-heater, leave power off for 10 seconds, and then restore power. The chiller-heater should start up if the WTO sensor reading is above the set point.
  • L
    lisarodriguezNov 11, 2025
    Why does my Yazaki CH-K30 Heater have poor cooling capacity?
    • S
      Sarah BrewerNov 11, 2025
      If your Yazaki Heater has poor cooling capacity, several factors could be responsible. Start by checking for poor vacuum and evacuate the machine per normal maintenance procedure; a leak check may also be necessary. High inlet cooling water temperature can also be a cause, so inspect the cooling tower fan and fluid level. Low cooling water flow rate is another possibility; check the cooling tower sump and cooling water circuit strainers. Condenser/Absorber fouling or scale buildup can also reduce cooling capacity, so check the cooling water circuit strainers and consider a chemical de-scaling procedure. Finally, if everything appears normal but the leaving chilled water temperature is too high, it could be that the load of the chilled water circuit exceeds the capacity of the chiller-heate...

Summary

General Information

Absorption Principle

Explains the working principle of lithium bromide and water absorption cycle.

Cooling Operation

Details the process of chilled water generation in the absorption cycle.

Heating Operation

Describes how the unit produces hot water using the absorption cycle.

Controls Overview

Control Panel General Information

Overview of the control panel and its functions for operation and supervision.

Control Adjustments

Unit Operation

Cooling Mode

Steps to engage and operate the unit in cooling mode.

Heating Mode

Steps to engage and operate the unit in heating mode.

Safety Controls

Monitors critical conditions and shuts down the unit upon abnormal events.

Remote Control

Explains how to enable and control the unit remotely.

Maintenance Procedures

Maintenance General Information

Emphasizes that maintenance should be done by trained personnel.

Routine Maintenance

Highlights the importance of regular maintenance for performance.

Maintenance Intervals

Lists recommended maintenance tasks at different time intervals.

Evacuation Overview

Details the importance and process of maintaining vacuum levels.

Chemical Maintenance

Focuses on inhibitor levels and chemical balance for the unit.

Troubleshooting Guide

Water Quality Requirements

Error Code Reference

Yazaki Limited Express Warranty

Yazaki CH-K30 Specifications

General IconGeneral
BrandYazaki
ModelCH-K30
CategoryHeater
LanguageEnglish

Related product manuals