3. Scope of Upgrade
3-3
TI 33K01B10-50E
3.2 Non-applicable Existing System
The following equipment can not be upgraded. Their recommended substitute products are
shown in the table.
Component
Table Recommended Substitute Products
Equipment out of
scope of upgrade
Recommended substitute Remarks
CFGW, EFGW (*1)
FFCS-V + ALR111/121
communication module
Subsystem communication package
(for serial communication, e.g., RS-232C, RS-485)
FFCS-V + ALE111
communication module
Subsystem communication package (for Ethernet)
CGWU,ECGWZ,
ECGW2, ECGW3
ACG, general purpose PC
Communications software should be restructured
with Exaopc.
EFUS, EFUD FFCS, FFCD
CFBS2 FFCS, FFCD
EMCS, EMCD FFCS, FFCD, APCS
CCMS, ECMP General-purpose PC
Application software should be restructured with
Exaquantum, Exaopc packages, etc.
XLAIS General-purpose PC Exapilot package
YEWLINK Optical repeater
*1: If CFGW or EFGW is used in the existing system, FIO’s communication modules (ALR111/ALR121 and ALE111 cards) should be
addedtotheeldcontrolstation(FCS).Applicationsoftwareshouldalsoberegenerated.
I/O Card
Table Recommended substitute device
Equipment of scope of upgrade Recommended substitute device Remarks
RS4 ALR111
Use new cables that support
different shape connectors. (*2)
*1: If the CFGW and EFGW are already incorporated in the existing system, FIO’s communication modules (ALR111/ALR121 and
ALE111cards)shouldbeincludedintheeldcontrolstation(FCS).Applicationsoftwareshouldalsoberegenerated.
*2: For details, see GS 33M50J10-40E for Cables.
Mar. 27, 2015-00