2. Heaters are 3 Phase.
ELECTRICAL DATA (FOR SINGLE SOURCE POWER SUPPLY) - COPPER WIRE 208/230-3-60
Models
Heat Kit -
Three Phase
Heater
Amps
240V
Field Wiring
Min. Circuit Ampacity
Max. O.C.P.
1
Amps/Type
75°C Wire Size - AWG
208V 240V 208V 240V 208V 240V
AHP24B**(N,H)21 4HK06501025 23.1 27.1 31.3 30 35 10 8
AHP30B**(N,H)21
4HK06501025 23.1 26.8 30.8 30 35 10 8
4HK065N1525 34.7 40.0 46.1 40 50 8 8
AHP36C**(N,H)21
4HK06501025 23.1 27.5 31.6 30 35 10 8
4HK06501525 34.7 40.0 46.1 40 50 8 8
AHP42C**(N,H)21
4HK06501025 23.1 29.1 33.4 30 35 10 8
4HK06501525 34.7 41.6 47.9 50 50 8 8
4HK06501825 41.4 48.9 56.3 50 60 8 6
AHP48D**(N,H)21
SHP48D**N21
4HK06501025 23.1 29.3 33.6 30 35 10 8
4HK06501525 34.7 41.8 48.1 50 50 8 8
4HK06501825 41.4 49.0 56.5 50 60 8 6
AHP60D**(N,H)21
SHP60D**N21
4HK06501025 23.1 34.5 38.4 35 40 8 8
4HK06501525 34.7 47.0 52.9 50 60 8 6
1. O.C.P. = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.
ELECTRICAL DATA (FOR MULTI SOURCE POWER SUPPLY) - COPPER WIRE 208/230-3-60
Models
Heater
Model
Minimum Circuit Ampacity
Max. O.C.P.
1
Amps/Type
75°C Wire Size - AWG
Circuit
1st 2nd 3rd 1st 2nd 3rd 1st 2nd 3rd
208/240 208/240 208/240 208/240 208/240 208/240 208/240 208/240 208/240
AHP60D**(N,H)21
SHP60D**N21
4HK16501825 31.9 / 35.4 22.4 / 25.9 - / - 35 / 40 25 / 30 - / - 8 / 8 10 / 10 - / -
4HK16502525 40.8 / 45.6 31.3 / 36.1 - / - 45 / 50 35 / 40 - / - 8 / 8 8 / 8 - / -
1. O.C.P. = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.