COOLING CAPACITY - With Air Handler Coils
UNIT
MODEL
AIR HANDLER
COIL
MODEL
1
COOLING
MODEL W STAGE
RATED
CFM
NET MBH SEER EER
CZE02411
AV24 17
1 650 18.5 14.9
15.00
12.70
2 825 24.0 19.0 12.00
AV36 21
1 625 18.5 14.9
15.00
13.20
2 800 24.0 19.0 12.50
MV12B 17 FC/MC36B
1 650 18.5 14.9
15.00
13.20
2 825 24.0 19.0 12.50
CZE03611
AV36 21
1 830 25.0 17.5
15.00
12.70
2 1200 35.0 25.4 12.15
AV/SV48 24
1 810 23.8 17.5
15.25
13.20
2 1200 36.0 26.3 12.50
MV12B 17 FC/MC42B
1 775 23.8 17.5
15.25
12.40
2 1200 35.0 26.3 12.00
MV16C 21 FC/MC48C
1 775 25.4 18.7
15.50
13.20
2 1185 36.0 27.2 12.50
MV12D 24 FC/MC48D
1 775 25.4 18.8
15.75
13.25
2 1185 36.0 27.2 12.50
MV20D 24 FC/MC48D
1 775 25.4 18.8
15.75
13.25
2 1185 36.0 27.2 12.50
CZE04811
AV/SV48 24
1 1130 33.4 25.1
15.00
13.20
2 1600 47.0 36.6 12.50
F*FV060 24
1 1000 33.4 25.1
15.75
13.20
2 1600 47.0 36.6 12.50
MV20D 24 FC/MC60D
1 1000 33.4 25.1
15.50
13.15
2 1600 47.0 36.6 12.50
MV20D 24 MC61D
1 1000 33.6 25.3
16.00
13.30
2 1560 47.0 37.1 12.50
CZE06011
AV/SV60 24
1 1145 39.0 29.5
13.75
11.60
2 1845 54.0 42.4 11.00
F*FV060 24
1 1200 39.0 29.5
13.75
11.60
2 1845 55.0 42.4 11.00
MV20D 24 FC/MC60D
1 1200 39.0 29.5
13.50
11.70
2 1845 54.5 42.5 11.00
MV20D 24 MC61D
1 1180 39.5 29.7
14.00
11.90
2 1850 55.0 42.7 11.50
Rated in accordance with DOE test procedures (Federal Register 12-27-79 and 3-18-88) and ARI Standards 210.
Cooling MBH based on 80°F entering air temperature, 50% RH, and rated air flow.
EER (Energy Efficiency Ratio) is the total cooling output in BTU’s at 95°F outdoor ambient divided by the total electric power in watt-hours at those conditions.
SEER (Seasonal Energy Efficiency Ratio) is the total cooling output in BTU’s during a normal annual usage period for cooling divided by the total electric power
input in watt-hours during the same period.
1. MC coils available with a factory installed horizontal drain pan. See price pages for specific model number.