571921-UTG-A-0410
12 Johnson Controls Unitary Products
CP equals MBH output divided by (total KW input x 3.412).
HSPF (Heating Seasonal Performance Factor) is the total heating output during a normal annual usage period for heating divided by the
total electric power input during the same period.
— = Not Applicable.
13 SEER HP WITH AHP / SHP / AHX / F*FP
GHGD18S41S3
AHP18 – 18.0 3.38 1.47 8.2 2.16 1.11 7.70
AHX18 – 18.0 3.58 1.47 8.6 2.52 1.11 7.95
F4FP024 – 18.0 3.34 1.49 12.5 3.04 1.21 7.70
F6FP018 – 18.0 3.58 1.47 8.6 2.52 1.11 7.95
F6FP024 – 18.0 3.64 1.49 9.9 2.52 1.11 8.20
GHGD24S41S4
AHP30 – 24.03.362.0913.92.381.717.70
F4FP040 – 24.03.362.0913.92.381.717.70
AHX30 – 24.03.621.9413.72.541.588.20
AHX36 – 24.03.621.9413.72.541.588.20
F6FP030 – 23.83.561.9613.62.521.588.20
F6FP036 – 23.63.601.9213.52.561.558.20
GHGD30S41S4
AHP30 – 27.43.302.4316.12.322.037.70
AHP36 – 27.83.382.4116.12.322.037.70
AHX30 – 27.23.482.2915.72.441.898.05
AHX36 – 27.23.642.1915.42.521.798.20
F4FP040 – 27.43.282.4516.02.302.047.70
F6FP030 – 27.23.362.3715.82.361.967.90
F6FP036 – 26.83.482.2615.42.461.838.00
GHGD36S41S4
AHP36 – 34.63.363.0222.42.582.548.00
AHX36 – 33.83.622.7421.62.802.268.20
F6FP042 – 34.43.702.7222.02.802.308.20
F5FP048 – 34.43.682.7421.82.802.288.20
F4FP045 – 35.43.562.9122.42.642.498.00
AHX42 – 33.83.702.6821.62.862.218.20
AHP42 – 34.83.482.9322.42.642.498.00
GHGD42S41S4
AHX42 – 35.63.642.8723.42.842.418.20
F6FP042 – 36.43.642.9323.82.802.498.20
AHP60 – 40.03.922.9922.42.642.498.20
AHP48 – 40.03.703.1722.82.502.677.70
AHX48 – 39.03.882.9522.22.682.438.20
F4FP045 – 40.53.743.1723.02.502.707.70
F5FP048 – 39.53.843.0122.62.642.518.20
F6FP048 – 39.53.962.9222.22.662.458.20
F5FP060 – 40.03.942.9722.62.662.498.20
GHGD48S41S4
AHP48 – 46.53.503.8927.62.722.977.70
AHP60 – 45.53.703.6027.02.842.797.70
AHX48 – 45.03.683.5826.62.862.738.20
AHX60 – 45.03.743.5326.42.922.658.20
F5FP060 – 46.03.703.6427.22.842.818.20
F6FP048 – 46.03.763.5827.02.902.738.20
F6FP060 – 45.03.743.5326.42.922.658.20
GHGD60S41S4
AHX60 – 57.03.404.9136.42.644.048.20
F6FP060 – 57.03.444.8536.42.664.018.20
1. Rated CFM same as for cooling.
2. Heating MBH based on ARI standards of 70° DB entering indoor air, 72% RH outdoor air with 25 feet of interconnecting piping and no
supplemental electric heat operation.
HEATING CAPACITY - With Air Handler (Continued)
UNIT
MODEL*
AIR
HANDLER
COIL
1
MODEL
ARI HEATING
2
47F17FHSPF
MBH COP KW MBH COP KW STD