550.13-TG2Y (799)
14 Unitary Products Group
TABLE 16: L*EU360 SUPPLY AIR BLOWER PERFORMANCE
1
RPM
CFM
SP
2
BHP
3
K
W
SP
2
BHP
3
K
W
SP
2
BHP
3
K
W
SP
2
BHP
3
K
W
SP
2
BHP
3
K
W
10,000 11,000 12,000 13,000 14,000
600
0.48 2.8 2.4 0.35 3.3 2.9 0.20 3.9 3.4 0.03 4.5 3.9 ——
635
4
0.62 3.1 2.7 0.49 3.7 3.2 0.35 4.3 3.7 0.19 4.9 4.2 0.03 5.5 4.7
700
5
0.87 3.8 3.3 0.76 4.4 3.8 0.63 5.0 4.3 0.49 5.6 4.8 0.34 6.3 5.4
775
6
1.21 4.7 4.1 1.11 5.3 4.6 0.99 5.9 5.1 0.86 6.5 5.6 0.72 7.2 6.2
800
7
1.30 4.9 4.2 1.20 5.5 4.8 1.08 6.2 5.4 0.95 6.9 6.0 0.81 7.6 6.6
875
8
1.64 5.9 5.1 1.54 6.5 5.6 1.43 7.1 6.1 1.32 7.8 6.7 1.20 8.6 7.4
900
1.75 6.2 5.4 1.66 6.8 5.9 1.55 7.4 6.4 1.44 8.1 7.0 1.33 8.9 7.7
970
9
2.10 7.2 6.2 2.00 7.8 6.7 1.90 8.5 7.3 1.81 9.2 7.9 1.71 10.0 8.6
1000
2.25 7.6 6.6 2.15 8.2 7.1 2.06 8.8 7.6 1.97 9.5 8.2 1.88 10.4 9.0
1.
Unit resistance is based on a wet evaporator coil and clean filters.
2.
Available static pressure in IWG to overcome the resistance of the duct system and any accessories added to the unit. Refer to
the blower motor and drive table and the accessory static resistance table for additional information.
3.
Motors can be selected to operate into the service factor because they are located in the moving air stream, upstream of any heat-
ing device. units with steam or hot water coils are the only exception. On these units, the BHP must not exceed the nominal HP
rating of the motor.
4.
Min. speed for drive accessory 1LD0415.
5.
Min. speed for drive accessory 1LD0414
6.
Min. speed for drive accessory 1LD0408
7.
Max. speed for drive accessory 1LD0415
8.
Max. speed for drive accessory 1LD0414
9.
Max. speed for drive accessory 1LD0406