Figure 5: Unit 4 Point Load Weight
Figure 6: Unit 6 Point Load Weight
Figure 7: Center of Gravity
All panels must be secured in place when the unit is
lifted.
The condenser coils should be protected from rigging
cable damage with plywood or other suitable material.
Table 2: Weights and Dimensions
Size
(Tons)
Model
Weight (lbs.) Center of Gravity 4 Point Load Location (lbs.) 6 Point Load Location (lbs.)
ShippingOperatingX Y ABCDABCDEF
037
(3)
ZR 887 867 40.3 25.5 205 170 223 269 141 124 110 144 163 185
049
(4)
ZR 900 880 40.9 25.1 202 172 232 273 139 124 112 151 168 187
061
(5)
ZR 887 867 41 25 198 169 230 269 136 122 110 150 166 184
Table 3: ZR037-061 Unit Accessory Weights
Unit Accessory
Weight (lbs.)
Shipping Operating
Economizer 90 85
Power Exhaust 40 35
Electric Heat
1
49 49
Gas Heat
2
110 110
1. Weight given is for the maximum heater size available (24KW).
2. Weight given is for the maximum number of tube heat exchangers
available (8 tube).