10
Sensible cooling capacities
Model
Dry tempera-
ture. outdoor
air
°C (DB)
Humid tempe-
rature.
air intake.
°C (WB)
Total
capacity
Sensible capacity (W)
Compressor
absorbed
power
kW
Dry intake air temperature to coil. °C (DB)
22 24 27 29
W W W W W
RTC20L
25
22 23 880 7 359 9 869 13 635 16 150 5.72
19.5 21 492 10 474 12 985 16 751 19 266 5.99
17 19 900 13 824 16 334 19 900 19 900 6.27
35
22 22 089 6 737 9 247 13 013 15 524 6.47
19.5 19 900 9 872 12 383 16 149 18 660 6.81
17 18 308 12 327 14 837 18 308 18 308 7.15
45
22 19 900 6 046 8 557 12 323 14 834 7.49
19.5 17 910 9 187 11 698 15 463 17 910 7.83
17 16 318 12 355 14 866 16 318 16 318 8.17
RTC25L
25
22 26 640 8 096 11 210 15 881 18 999 6.75
19.5 23 976 11 981 15 094 19 765 22 884 7.08
17 22 200 16 120 19 234 22 200 22 200 7.40
35
22 24 642 7 418 10 532 15 203 18 317 7.64
19.5 22 200 11 323 14 437 19 107 22 200 8.04
17 20 424 14 509 17 623 20 424 20 424 8.44
45
22 22 200 6 664 9 778 14 449 17 563 8.84
19.5 19 980 10 572 13 686 18 357 19 980 9.25
17 18 204 14 511 17 625 18 204 18 204 9.65
RTC30L
25
22 32 400 10 028 13 328 18 277 21 582 7.56
19.5 29 160 14 116 17 415 22 365 25 670 7.92
17 27 000 18 522 21 822 26 771 27 000 8.28
35
22 29 970 9 178 12 478 17 427 20 727 8.55
19.5 27 000 13 293 16 593 21 543 24 842 9.00
17 24 840 16 659 19 958 24 840 24 840 9.45
45
22 27 000 8 235 11 535 16 484 19 784 9.90
19.5 24 300 12 358 15 657 20 607 23 906 10.35
17 22 140 16 518 19 818 22 140 22 140 10.80