Overview of the Style B LCSSS, its features, and application with OptiView Control Center.
Details the water-to-water heat exchanger and coolant system for SCR cooling.
Outlines circuits protecting the motor from high current and other fault conditions.
Describes shutdown for motor current exceeding 105% of FLA for 40 seconds.
Explains shutdown due to SCR heatsink temperature exceeding 212°F.
Details shutdown when motor current exceeds a peak threshold for one second.
Details shutdown for phase current imbalance exceeding 30% of average for 45 seconds.
Explains shutdown when an SCR fails to turn on or is improperly gated.
Describes shutdown due to incorrect input power phase rotation during startup.
Details shutdown when an SCR is detected as shorted.
Explains shutdown when input voltage exceeds thresholds for 20 continuous seconds.
Describes shutdown due to failed communication between Micro Board and Logic/Trigger Board.
Details shutdown caused by improper current transformer connections or scaling.