036-21121-002 Rev. A (0602)
18 Unitary Products Group
Multipliers for determining the performance with other indoor sections.
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO. H1RA090S(25,46)
INDOOR COIL MODEL NO. K4EV090
CONDENSER
ENTERING AIR
TEMPERATURE
ID CFM 2400 3000 3600
ID DB (°F) 85 80 70 85 80 70 85 80 70
ID WB (°F) 72 67 57 72 67 57 72 67 57
75
T.C. 104.2 97.2 90.1 108.1 100.5 92.8 112.1 103.8 95.5
S.C. 76.5 71.0 65.6 78.7 72.8 66.9 81.0 74.6 68.2
K.W 8.30 8.21 8.13 8.33 8.25 8.18 8.36 8.29 8.23
85
T.C. 99.1 92.4 85.8 102.0 94.7 87.5 104.8 97.0 89.1
S.C. 72.5 67.4 62.3 74.0 68.4 62.8 75.5 69.4 63.4
K.W 8.97 8.86 8.75 9.01 8.90 8.79 9.04 8.94 8.84
95
T.C. 94.0 87.7 81.5 95.8 89.0 82.1 97.5 90.1 82.7
S.C. 68.6 63.8 59.0 69.3 64.0 58.7 70.0 64.2 58.5
K.W 9.64 9.50 9.37 9.68 9.55 9.41 9.72 9.59 9.45
105
T.C. 88.2 82.2 76.1 89.8 83.9 77.9 91.4 85.6 79.7
S.C. 68.7 63.7 58.7 69.2 64.3 59.4 69.8 64.9 60.1
K.W 10.33 10.14 9.96 10.38 10.21 10.03 10.43 10.27 10.10
115
T.C. 82.5 76.6 70.8 83.9 78.8 73.8 85.3 81.0 76.7
S.C. 59.9 55.4 50.9 60.2 56.3 52.4 60.5 57.2 53.9
K.W 11.02 10.79 10.55 11.08 10.87 10.65 11.14 10.95 10.76
125
T.C. 76.7 71.1 65.5 78.0 73.8 69.6 79.2 76.5 73.7
S.C. 55.5 51.2 46.8 55.7 52.4 49.2 55.8 53.7 51.6
K.W 11.71 11.43 11.15 11.78 11.53 11.28 11.86 11.63 11.41
NOTE:
ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
Coil
T.C. S.C. KW
G2FD090S35 1.01 1.01 1.01