036-21121-002 Rev. A (0602)
Unitary Products Group 9
Multipliers for determining the performance with other indoor sections.
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO. H1RA018S06
INDOOR COIL MODEL NO. G1FA024S14,17
CONDENSER
ENTERING AIR
TEMPERATURE
ID CFM 550 650 750
ID DB (°F) 85 80 70 85 80 70 85 80 70
ID WB (°F) 72 67 57 72 67 57 72 67 57
75
T.C. 20.6 19.7 18.1 20.7 19.8 18.5 20.8 19.8 18.9
S.C. 12.7 12.8 12.3 13.3 13.5 13.4 13.7 13.8 14.0
K.W 1.68 1.65 1.64 1.72 1.71 1.70 1.75 1.74 1.73
85
T.C. 20.6 19.3 17.4 20.9 19.6 18.0 21.1 19.8 18.4
S.C. 12.7 12.6 11.9 13.5 13.4 13.1 14.1 14.0 13.8
K.W 1.58 1.54 1.53 1.62 1.59 1.58 1.65 1.63 1.62
95
T.C. 19.0 17.5 15.5 19.5 18.0 16.1 19.8 18.2 16.5
S.C. 12.8 12.4 11.5 13.7 13.3 12.8 14.5 14.1 13.6
K.W 1.97 1.91 1.90 2.02 1.96 1.95 2.05 2.00 1.99
105
T.C. 18.4 16.6 14.2 18.9 17.1 15.0 19.2 17.4 15.4
S.C. 12.5 11.8 10.7 13.6 12.8 12.0 14.4 13.7 12.8
K.W 1.82 1.77 1.75 1.88 1.82 1.80 1.91 1.86 1.83
115
T.C. 16.3 14.5 11.9 16.9 15.0 12.7 17.2 15.2 13.1
S.C. 12.3 11.2 10.0 13.5 12.4 11.2 14.3 13.2 12.0
K.W 2.24 2.19 2.14 2.31 2.24 2.19 2.35 2.28 2.22
125
T.C. 14.3 12.3 9.7 14.9 13.0 10.5 15.2 13.1 10.8
S.C. 12.0 10.6 9.3 13.3 11.9 10.4 14.2 12.8 11.2
K.W 2.66 2.61 2.53 2.74 2.66 2.58 2.79 2.70 2.61
NOTE:
ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM
Air Handler Coil
T.C. S.C. KW
N1AHB0806 G2FD024S17 1.06 1.06 0.99
F2RC/F2FC024 0.97 0.97 0.99
G1FA030S14 1.06 1.06 0.99
G1HD024 1.03 1.03 0.95
G1NA024S17G 1.00 0.94 0.98
G1UA024S14,17 1.00 1.00 1.00
G1UA030S14 1.06 1.06 0.99
G2FD024S14,17 1.06 1.06 0.99
G2FD030S17 1.08 1.08 1.00
G2FD035S14 1.08 1.08 1.00

Related product manuals