5581709-YTG-C-0619
Johnson Controls Ducted Systems 9
— = Not applicable.
MP Modular Air Handlers use Coil Only Ratings.
YCD60B21S AE60CX21 21.0 1625 56.0 40.0 13.25 11.25
YCD60B21S AE60DX21 24.5 1775 57.0 41.5 13.25 11.25
YCD60B21S AP60CX21 21.0 1525 54.5 38.0 13.00 10.75
YCD60B21S AP60DX22 24.5 1525 55.0 38.0 13.00 10.75
YCD60B21S AVC60CX21 21.0 1750 56.0 41.0 13.00 11.25
YCD60B21S AVC60DX21 24.5 1650 56.5 40.5 13.50 11.25
YCD60B21S ME16CN21 21.0 CF/CM60C 1625 56.0 40.0 13.50 11.25
YCD60B21S ME20DN21 24.5 CF/CM60D 1650 56.0 40.0 13.50 11.25
YCD60B21S ME20DN21 24.5 CF/CM64D 1625 56.5 40.5 13.50 11.50
YCD60B21S MVC16CN21 21.0 CF/CM60C 1650 56.5 40.5 14.25 12.00
YCD60B21S MVC20DN21 24.5 CF/CM60D 1700 56.0 40.0 13.50 11.25
YCD60B21S MVC20DN21 24.5 CF/CM64D 1700 56.5 40.0 13.50 11.25
Rated in accordance with DOE test procedures (Federal Register 12-27-79 and 3-18-88) and ANSI/AHRI Standard 210/240.
Cooling MBH based on 80°F entering air temperature, 50% RH (Relative Humidity), and rated air flow.
EER (Energy Efficiency Ratio) is the total cooling output in BTUs at 95°F outdoor ambient divided by the total electric power in watt-hours at those conditions.
SEER (Seasonal Energy Efficiency Ratio) is the total cooling output in BTUs during a normal annual usage period for cooling divided by the total
electric power input in watt-hours during the same period.
1. CM coils available with a factory installed horizontal drain pan. See price pages for specific model number.
COOLING CAPACITY - With Air Handler Coils (Continued)
UNIT
MODEL
AIR HANDLER
COIL
MODEL
1
COOLING
MODEL WIDTH
RATED
CFM
NET MBH
SEER EER
TOTAL SENS.
COOLING CAPACITY - Upflow, Downflow & Horizontal Furnaces and Coils (Coil Only Ratings)
UNIT MODEL
COIL
CFM RANGE
(MIN.-MAX.)
COOLING
MODEL WIDTH
RATED
CFM
NET MBH
SEER
1
EER
TOTAL SENS.
YCD18B22S CF/CM/CU18A 14.5 450 - 750 600 17.2 13.0 13.00 11.50
YCD18B22S CF/CM/CU18B 17.5 450 - 750 600 17.2 13.8 13.00 11.50
YCD18B22S CF/CM/CU24A 14.5 450 - 750 600 17.4 13.9 13.00 11.50
YCD18B22S CF/CM/CU24B 17.5 450 - 750 600 17.4 13.9 13.00 11.50
YCD18B22S CF/CM/CU30A 14.5 450 - 750 600 17.6 14.1 13.00 11.50
YCD18B22S CF/CM/CU30B 17.5 450 - 750 600 17.6 14.1 13.00 11.50
YCD18B22S CF/CM/CU36B 17.5 450 - 750 600 17.6 14.0 13.25 11.75
YCD18B22S CF/CM/CU36C 21.0 450 - 750 600 17.6 14.0 13.25 11.75
YCD18B22S CF/CM24C 21.0 450 - 750 600 17.4 13.9 13.00 11.50
YCD18B22S CF/CM30C 21.0 450 - 750 600 17.6 14.1 13.00 11.50
YCD18B22S CF/CM36A 14.5 450 - 750 600 17.6 14.0 13.25 11.75
YCD18B22S CF/CM36D 24.5 450 - 750 600 17.6 14.0 13.25 11.75
YCD24B22S CF/CM/CU24A 14.5 600 - 1000 800 23.0 16.1 13.00 11.50
YCD24B22S CF/CM/CU30A 14.5 600 - 1000 800 23.0 18.3 13.00 11.50
YCD24B22S CF/CM/CU30B 17.5 600 - 1000 800 23.0 18.3 13.00 11.50
YCD24B22S CF/CM/CU36B 17.5 600 - 1000 800 23.4 18.5 13.00 11.50
YCD24B22S CF/CM/CU36C 21.0 600 - 1000 800 23.4 18.5 13.00 11.50
YCD24B22S CF/CM/CU42C 21.0 600 - 1000 800 23.6 18.7 13.00 11.50
YCD24B22S CF/CM30C 21.0 600 - 1000 800 23.0 18.3 13.00 11.50
YCD24B22S CF/CM36A 14.5 600 - 1000 800 23.6 18.7 13.00 11.50
YCD24B22S CF/CM36D 24.5 600 - 1000 800 23.4 18.5 13.00 11.50
YCD24B22S CF/CM42D 24.5 600 - 1000 800 23.6 18.7 13.00 11.50
YCD24B22S CF42B 17.5 600 - 1000 800 23.4 18.5 13.00 11.50
YCD30B22S CF/CM/CU30B 17.5 800 - 1200 1000 28.6 21.4 13.00 11.00
YCD30B22S CF/CM/CU36B 17.5 800 - 1200 1000 29.0 23.0 13.00 11.25
YCD30B22S CF/CM/CU36C 21.0 800 - 1200 1000 29.0 23.0 13.00 11.25
YCD30B22S CF/CM/CU42C 21.0 800 - 1200 1000 29.0 22.8 13.00 11.25
YCD30B22S CF/CM30C 21.0 800 - 1200 1000 28.8 22.8 13.00 11.00
YCD30B22S CF/CM36D 24.5 800 - 1200 1000 29.0 23.0 13.00 11.25