21ºC 25ºC 30ºC 35ºC 40ºC 45ºC 50ºC
Total capacity kW
8.50 8.13 7.84 7.39 7.10 6.87 6.65
Sensitive capacity kW
6.80 6.50 6.27 5.91 5.68 5.50 5.32
21ºC D
15ºC W
Input kW.
2.05 2.34 2.63 2.93 3.22 3.51 3.80
Total capacity kW
9.31 8.91 8.58 8.10 7.77 7.53 7.29
Sensitive capacity kW
7.45 7.12 6.87 6.48 6.22 6.02 5.83
24ºC D
17ºC W
Input kW.
2.16 2.47 2.78 3.09 3.40 3.71 4.01
Total capacity kW
10.12 9.68 9.33 8.80 8.45 8.18 7.92
Sensitive capacity kW
8.10 7.74 7.46 7.04 6.76 6.55 6.34
27ºC D
19ºC W
Input kW.
2.28 2.60 2.93 3.25 3.58 3.90 4.23
Total capacity kW
11.64 11.13 10.73 10.12 9.72 9.41 9.11
Sensitive capacity kW
9.31 8.91 8.58 8.10 7.77 7.53 7.29
32ºC D
23ºC W
Input kW.
2.62 2.99 3.36 3.74 4.11 4.49 4.86
Model: YKHC-30
HEATING OUTDOOR CONDITIONS
Indoor
Conditions
24ºC D
-6ºC W
-7ºC D
-8ºC W
-15ºC D
-16ºC W
Capacity kW
11.28 9.02 7.52 6.77 6.39 5.64 5.26 4.89
15ºC
Input kW.
3.90 3.12 2.60 2.47 2.34 2.21 2.08 1.82
Capacity kW
12.69 10.15 8.46 7.61 7.19 6.35 5.92 5.50
18ºC
Input kW.
4.39 3.51 2.93 2.78 2.63 2.49 2.34 2.05
Capacity kW
14.10 11.28 9.40 8.46 7.99 7.05 6.58 6.11
20ºC
Input kW.
4.88 3.90 3.25 3.09 2.93 2.76 2.60 2.28
Capacity kW
15.51 12.41 10.34 9.31 8.79 7.76 7.24 6.72
22ºC
Input kW.
5.36 4.29 3.58 3.40 3.22 3.04 2.86 2.50
Capacity kW
18.33 14.66 12.22 11.00 10.39 9.17 8.55 7.94
27ºC
Input kW.
6.34 5.07 4.23 4.01 3.80 3.59 3.38 2.96