21ºC 25ºC 30ºC 35ºC 40ºC 45ºC 50ºC
Total capacity kW
10.14 9.70 9.35 8.82 8.47 8.20 7.94
Sensitive capacity kW
8.11 7.76 7.48 7.06 6.77 6.56 6.35
21ºC D
15ºC W
Input kW.
2.33 2.66 3.00 3.33 3.66 4.00 4.33
Total capacity kW
11.11 10.63 10.24 9.66 9.27 8.98 8.69
Sensitive capacity kW
8.89 8.50 8.19 7.73 7.42 7.19 6.96
24ºC D
17ºC W
Input kW.
2.46 2.81 3.16 3.52 3.87 4.22 4.57
Total capacity kW
12.08 11.55 11.13 10.50 10.08 9.77 9.45
Sensitive capacity kW
9.66 9.24 8.90 8.40 8.06 7.81 7.56
27ºC D
19ºC W
Input kW.
2.59 2.96 3.33 3.70 4.07 4.44 4.81
Total capacity kW
13.89 13.28 12.80 12.08 11.59 11.23 10.87
Sensitive capacity kW
11.11 10.63 10.24 9.66 9.27 8.98 8.69
32ºC D
23ºC W
Input kW.
2.98 3.40 3.83 4.26 4.68 5.11 5.53
Model: YKHC-36
HEATING OUTDOOR CONDITIONS
Indoor
Conditions
24ºC D
-6ºC W
-7ºC D
-8ºC W
-15ºC D
-16ºC W
Capacity kW
13.68 10.94 9.12 8.21 7.75 6.84 6.38 5.93
15ºC
Input kW.
4.02 3.22 2.68 2.55 2.41 2.28 2.14 1.88
Capacity kW
15.39 12.31 10.26 9.23 8.72 7.70 7.18 6.67
18ºC
Input kW.
4.52 3.62 3.02 2.86 2.71 2.56 2.41 2.11
Capacity kW
17.10 13.68 11.40 10.26 9.69 8.55 7.98 7.41
20ºC
Input kW.
5.03 4.02 3.35 3.18 3.02 2.85 2.68 2.35
Capacity kW
18.81 15.05 12.54 11.29 10.66 9.41 8.78 8.15
22ºC
Input kW.
5.53 4.42 3.69 3.50 3.32 3.13 2.95 2.58
Capacity kW
22.23 17.78 14.82 13.34 12.60 11.12 10.37 9.63
27ºC
Input kW.
6.53 5.23 4.36 4.14 3.92 3.70 3.48 3.05