32
d01 U 7 (R/W) - 1 0 1 1
d02 U 8 (R/W) - 1 0 1 1
d03 Defrost start temperature U 19 (R/W) °C d04 -40 -1 -1
d04 Defrost end temperature U 21 (R/W) °C 80 d03 5 5
d05 Minimum time for defrost start U 37 (R/W) Sec 150 10 60 60
d06 Minimum duration of defrost U 38 (R/W) Sec 150 0 0 0
d07 Maximum duration of defrost U 39 (R/W) Min. 15 1 10 10
d08 Time between two defrost cycles U 40 (R/W) Min. 150 10 30 30
d09
Defrost delay between the two circuits U 41 (R/W) Min. 150 0 10 10
d10 External contact defrost F 42 (R/W) - 3 0 2 0
d11 U 9 (R/W) - 0 1 0 0
d12 Compressor OFF prior to defrost F 43 (R/W) Min. 3 0 0 0
d13 Compressor OFF after defrost F 44 (R/W) Min. 3 0
d16 F 47 (R/W) Sec 360 0 0 0
Parameters related to defrost
Execution of defrost 0 = no; 1 = yes
Defrost based on time or temperature
0 = time (function not available)
1 = temperature
Forced ventilation time at the end of defrost
(only if F13 = 2).
Activation of heaters in defrost
0 = no
1 = yes