EasyManua.ls Logo

York YLCC-122 - Temperature Tables:; NTC probe (10 KOhm) water intake, water and liquid outlet.

York YLCC-122
84 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
82
-50 329.20
-49 310.70
-48 293.30
-47 277.00
-46 261.80
-45 247.50
-44 234.10
-43 221.80
-42 209.80
-41 198.70
-40 188.40
-39 178.30
-38 168.90
-37 160.10
-36 151.80
-35 144.00
-34 136.60
-33 129.70
-32 123.20
-31 117.10
-30 111.30
-29 106.70
-28 100.40
-27 95.47
-26 90.80
-25 86.39
-24 82.22
-23 78.29
-22 74.58
-21 71.07
-20 67.74
-19 64.54
-18 61.62
-17 58.66
-16 55.95
-15 53.99
-14 50.90
-13 48.66
-12 46.48
-11 44.41
-10 42.45
-9 40.56
-8 38.76
-7 37.05
-6 35.48
-5 33.89
-4 32.43
-3 31.04
-2 29.72
-1 28.47
0 27.28
1 26.13
2 25.03
3 23.09
4 22.09
5 22.05
6 21.15
7 20.20
8 19.48
9 18.70
10 17.98
11 17.24
12 16.55
13 15.90
14 15.28
15 14.68
16 14.12
17 13.57
18 13.08
19 12.58
20 12.09
21 11.83
22 11.20
23 10.78
24 10.38
25 10.00
Temperature tables:
The following table indicates the ratio between the probe
temperature and resistance.
NTC probe (10 KOhm) water intake, water and liquid outlet.
Resistance
(Kohms)
Temperature
(° C)
Resistance
(Kohms)
Temperature
(° C)

Related product manuals