EasyManua.ls Logo

York YUHC 18 - Capacity Tables: YUHC-36

York YUHC 18
49 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Model: YUHC-36
COOLING OUTDOOR CONDITIONS
Indoor
Conditions
21ºC 25ºC 30ºC 35ºC 40ºC 45ºC 50ºC
Total capacity kW
10.14 9.70 9.35 8.82 8.47 8.20 7.94
Sensitive capacity kW
8.11 7.76 7.48 7.06 6.77 6.56 6.35
21ºC D
15ºC W
Input kW.
2.33 2.66 3.00 3.33 3.66 4.00 4.33
Total capacity kW
11.11 10.63 10.24 9.66 9.27 8.98 8.69
Sensitive capacity kW
8.89 8.50 8.19 7.73 7.42 7.19 6.96
24ºC D
17ºC W
Input kW.
2.46 2.81 3.16 3.52 3.87 4.22 4.57
Total capacity kW
12.08 11.55 11.13
10.50
10.08 9.77 9.45
Sensitive capacity kW
9.66 9.24 8.90 8.40 8.06 7.81 7.56
27ºC D
19ºC W
Input kW.
2.59 2.96 3.33
3.70
4.07 4.44 4.81
Total capacity kW
13.89 13.28 12.80 12.08 11.59 11.23 10.87
Sensitive capacity kW
11.11 10.63 10.24 9.66 9.27 8.98 8.69
32ºC D
23ºC W
Input kW.
2.98 3.40 3.83 4.26 4.68 5.11 5.53
HEATING OUTDOOR CONDITIONS
Indoor
Conditions
24ºC D
18ºC W
12ºC D
11ºC W
7ºC D
6ºC W
4ºC D
3ºC W
0ºC D
-1ºC W
-5ºC D
-6ºC W
-7ºC D
-8ºC W
-15ºC D
-16ºC W
Capacity kW
14.40 11.52 9.60 8.64 8.16 7.20 6.72 6.24
15ºC
Input kW.
4.02 3.22 2.68 2.55 2.41 2.28 2.14 1.88
Capacity kW
16.20 12.96 10.80 9.72 9.18 8.10 7.56 7.02
18ºC
Input kW.
4.52 3.62 3.02 2.86 2.71 2.56 2.41 2.11
Capacity kW
18.00 14.40
12.00
10.80 10.20 9.00 8.40 7.80
20ºC
Input kW.
5.03 4.02
3.35
3.18 3.02 2.85 2.68 2.35
Capacity kW
19.80 15.84 13.20 11.88 11.22 9.90 9.24 8.58
22ºC
Input kW.
5.53 4.42 3.69 3.50 3.32 3.13 2.95 2.58
Capacity kW
23.40 18.72 15.60 14.04 13.26 11.70 10.92 10.14
27ºC
Input kW.
6.53 5.23 4.36 4.14 3.92 3.70 3.48 3.05