EasyManua.ls Logo

York YUHC 18 - Heating Mode Operations; Compressor and Fan Conditions; Indoor Fan Control in Heating

York YUHC 18
49 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3.2 Heating Mode
3.2.1 Four-way valve opens at once, while defrosting process closes.
3.2.2 Condition for the compressor action: (Ts = set temperature, Ta = room temperature)
Condition Compressor Outdoor fan
Ta > Ts+4
Off Off
Room temp. up
Ta <Ts+4
On On
Ta < Ts+3
On On
Room temp. down
Ta >Ts+3
Off Off
3.2.3 Indoor Fan Action
3.2.3.1 Anytime remote switchover for fan speed among high/low/auto(anti-cold air function takes priority).
3.2.3.2 Anti-cold air:
Switchover between fan speed and fine tune can be set according to temperature of evaporator pipe.
Condition
T= Indoor exchanger temp.
Indoor fan speed
T<25°C Off
25°C <T<32°C Breeze
Indoor exchanger temp. up
T>32°C Setting fan speed
T> 30°C Setting fan speed
15°C <T<30°C Breeze
Indoor exchanger temp. down
T<15°C Off
During anti-cold air period, if indoor fan is shut down, then pre-heating/defrosting lamp is on. Once indoor
fan starts, pre-heating/defrosting lamp will be off.
3.2.3.3 Auto fan of indoor fan under heating mode.
Condition (T =Indoor Temp.-Setting Temp.) Indoor fan speed
T<3°C High Room temp. up
T>3°C Low
T> 1°C Low Room temp. down
T<1°C High

Related product manuals