COOLING OUTDOOR CONDITIONS
Indoor
Conditions
21ºC 25ºC 30ºC 35ºC 40ºC 45ºC 50ºC
Total capacity kW
15.46 14.78 14.25 13.44 12.90 12.50 12.10
Sensitive capacity kW
12.36 11.83 11.40 10.75 10.32 10.00 9.68
21ºC D
15ºC W
Input kW.
3.78 4.32 4.86 5.40 5.94 6.48 7.02
Total capacity kW
16.93 16.19 15.60 14.72 14.13 13.69 13.25
Sensitive capacity kW
13.54 12.95 12.48 11.78 11.30 10.95 10.60
24ºC D
17ºC W
Input kW.
3.99 4.56 5.13 5.70 6.27 6.84 7.41
Total capacity kW
18.40 17.60 16.96
16.00
15.36 14.88 14.40
Sensitive capacity kW
14.72 14.08 13.57 12.80 12.29 11.90 11.52
27ºC D
19ºC W
Input kW.
4.20 4.80 5.40
6.00
6.60 7.20 7.80
Total capacity kW
21.16 20.24 19.50 18.40 17.66 17.11 16.56
Sensitive capacity kW
16.93 16.19 15.60 14.72 14.13 13.69 13.25
32ºC D
23ºC W
Input kW.
4.83 5.52 6.21 6.90 7.59 8.28 8.97
HEATING OUTDOOR CONDITIONS
Indoor
Conditions
24ºC D
18ºC W
12ºC D
11ºC W
7ºC D
6ºC W
4ºC D
3ºC W
0ºC D
-1ºC W
-5ºC D
-6ºC W
-7ºC D
-8ºC W
-15ºC D
-16ºC W
Capacity kW
24.00 19.20 16.00 14.40 13.60 12.00 11.20 10.40
15ºC
Input kW.
7.20 5.76 4.80 4.56 4.32 4.08 3.84 3.36
Capacity kW
27.00 21.60 18.00 16.20 15.30 13.50 12.60 11.70
18ºC
Input kW.
8.10 6.48 5.40 5.13 4.86 4.59 4.32 3.78
Capacity kW
30.00 24.00
20.00
18.00 17.00 15.00 14.00 13.00
20ºC
Input kW.
9.00 7.20
6.00
5.70 5.40 5.10 4.80 4.20
Capacity kW
33.00 26.40 22.00 19.80 18.70 16.50 15.40 14.30
22ºC
Input kW.
9.90 7.92 6.60 6.27 5.94 5.61 5.28 4.62
Capacity kW
39.00 31.20 26.00 23.40 22.10 19.50 18.20 16.90
27ºC
Input kW.
11.70 9.36 7.80 7.41 7.02 6.63 6.24 5.46