EasyManua.ls Logo

York ZD Series - Page 21

York ZD Series
81 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5188236-BIM-A-0316
Johnson Controls Unitary Products 21
ZD-03 Thru -05 - Without Powered Convenience Outlet (Direct Drive)
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Conv
Outlet
Electric Heat Option
MCA
1
(Amps)
Max
Fuse
2
/
Breaker
3
Size
(Amps)
RLA LRA MCC FLA FLA FLA Model kW Stages Amps
-03
(3.0)
208-1-60 15.4 83.9 24 2.3 6 0
NONE - - - 27.5 35
E05 4 1 19.2 31.5 40
E07 5.6 1 26.9 41.2 45
E10 8 1 38.5 55.6 60
E15 11.9 2 57.2 79 80
E20 15.9 2 76.4 103.1 110
230-1-60 15.4 83.9 24 2.3 6 0
NONE - - - 27.5 35
E05 5.3 1 22.1 35.1 40
E07 7.5 1 31.2 46.6 50
E10 10.6 1 44.2 62.7 70
E15 15.9 2 66.2 90.3 100
E20 21.2 2 88.3 117.9 125
208-3-60 10.4 73 16.3 2.3 6 0
NONE - - - 21.3 30
E05 4 1 11.1 21.4 30
E07 5.6 1 15.5 26.9 30
E10 8 1 22.2 35.3 40
E15 11.9 2 33 48.8 50
E20 15.9 2 44.1 62.7 70
230-3-60 10.4 73 16.3 2.3 6 0
NONE - - - 21.3 30
E05 5.3 1 12.7 23.4 30
E07 7.5 1 18 30.1 35
E10 10.6 1 25.5 39.4 40
E15 15.9 2 38.2 55.3 60
E20 21.2 2 51 71.2 80
-04
(4.0)
208-1-60 19.6 130 30.5 2.3 7.6 0
NONE - - - 34.4 45
E05 4 1 19.2 34.4 45
E07 5.6 1 26.9 43.2 50
E10 8 1 38.5 57.6 60
E15 11.9 2 57.2 81 90
E20 15.9 2 76.4 105.1 110
230-1-60 19.6 130 30.5 2.3 7.6 0
NONE - - - 34.4 45
E05 5.3 1 22.1 37.1 45
E07 7.5 1 31.2 48.6 50
E10 10.6 1 44.2 64.7 70
E15 15.9 2 66.2 92.3 100
E20 21.2 2 88.3 119.9 125
208-3-60 13.7 83.1 21.4 2.3 7.6 0
NONE - - - 27 35
E05 4 1 11.1 27 35
E07 5.6 1 15.5 28.9 35
E10 8 1 22.2 37.3 40
E15 11.9 2 33 50.8 60
E20 15.9 2 44.1 64.7 70
230-3-60 13.7 83.1 21.4 2.3 7.6 0
NONE - - - 27 35
E05 5.3 1 12.7 27 35
E07 7.5 1 18 32.1 40
E10 10.6 1 25.5 41.4 45
E15 15.9 2 38.2 57.3 60
E20 21.2 2 51 73.2 80

Table of Contents